2016-08-19 12:46:17 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) SHEET FP 501 - THERE IS NO INDICATIONS THAT ELBOWS |
| AND T'S ARE GREATER THAN 10 THE SUCTION PIPE DIAMETER. |
| |
| |
| 4.14.6.3 ELBOWS AND TEES. |
| 4.14.6.3.1 UNLESS THE REQUIREMENTS OF 4.14.6.3.2 ARE |
| MET, ELBOWS AND TEES WITH A CENTERLINE PLANE PARALLEL |
| TO A HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE |
| PERMITTED. (SEE FIGURE A.4.14.6.) |
| 4.14.6.3.2 THE REQUIREMENTS OF 4.14.6.3.1 SHALL NOT |
| APPLY TO ELBOWS AND TEES WITH A CENTERLINE PLANE |
| PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT WHERE |
| THE DISTANCE BETWEEN THE FLANGES OF THE PUMP SUCTION |
| INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10 TIMES |
| THE SUCTION PIPE DIAMETER. |
| 4.14.6.3.3 ELBOWS WITH A CENTERLINE PLANE PERPENDICULAR |
| TO THE HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL BE |
| PERMITTED AT ANY LOCATION IN THE PUMP SUCTION INTAKE. |
| |
| |
| PLEASE ENSURE COMPLIANCE ON INSTALLATION. FIRE |
| INSPECTOR WILL VERIFY ON INSPECTION. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |