2016-08-19 12:46:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET FP 501 - THERE IS NO INDICATIONS THAT ELBOWS
 AND T'S ARE GREATER THAN 10 THE SUCTION PIPE DIAMETER.
  
  
 4.14.6.3 ELBOWS AND TEES.
 4.14.6.3.1 UNLESS THE REQUIREMENTS OF 4.14.6.3.2 ARE
 MET, ELBOWS AND TEES WITH A CENTERLINE PLANE PARALLEL
 TO A HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE
 PERMITTED. (SEE FIGURE A.4.14.6.)
 4.14.6.3.2 THE REQUIREMENTS OF 4.14.6.3.1 SHALL NOT
 APPLY TO ELBOWS AND TEES WITH A CENTERLINE PLANE
 PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT WHERE
 THE DISTANCE BETWEEN THE FLANGES OF THE PUMP SUCTION
 INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10 TIMES
 THE SUCTION PIPE DIAMETER.
 4.14.6.3.3 ELBOWS WITH A CENTERLINE PLANE PERPENDICULAR
 TO THE HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL BE
 PERMITTED AT ANY LOCATION IN THE PUMP SUCTION INTAKE.
  
  
 PLEASE ENSURE COMPLIANCE ON INSTALLATION. FIRE
 INSPECTOR WILL VERIFY ON INSPECTION.
  
  