Plan Review Notes
Plan Review Notes For Permit 16040539
Permit Number 16040539
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-08-08 13:06:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NUMEROUS COMMENTS WERE NOT PROVIDED WITH ANY NARRATIVE,
 NOTE OR REVISION CLOUD. PER NPFA 1
  
 1.14 PLAN REVIEW.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
 PREVIOUS COMMENTS:
  
 1) SHEET FP 110 A - COMPLIED WITH LETTER.
  
 2) SHEET FP 110 A - COMPLIED WITH LETTER.
  
 3) SHEET FP 110 C - REMOTE AREA # 1 INDICATES
 0.100GPM/FT2 AND THE CLACULATIONS SHEETS INDICATES
 0.15GPM/FT2. PLEASE CORRECT AND CLARIFY WHICH IS
 CORRECT.
  
 REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT
 SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF THE
 REMOTE AREA.
  
 4) SHEET FP 110 C - REMOTE AREA # 1 LAYOUT IS DIFFICULT
 TO DETERMINE AS THERE APPEARS TO BE TWO SETS OF BRANCH
 LINES IN THE SAME AREA. PLEASE CLARIFY OR SHOW
 ELEVATIONS.
  
 REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT
 SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF
 CLARITY.
  
 5) SHEET FP 110 C - PLEASE PROVIDE AND INDICATE EXACT
 DIMENSIONS AND SQUARE FOOTAGE OF ACTUAL REMOTE AREA #
 1. NO DIMENSIONS ARE INDICATED AND THE AREA IS NOT
 CLEARLY MARKED.
  
 REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT
 SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF
 CLARITY.
  
 6) SHEET FP 120 A - ALL THE ROOMS ARE NOT LABELED. ALL
 ROOMS SHALL BE LABELED OR INDICATED. THERE ARE TWO
 ROOMS WITH 1 SPRINKLER HEAD ONLY THAT APPEAR TO BE FOR
 ORDINARY HAZARD GROUP 1. WERE THE CALCULATION DEMANDS
 OF THESE HEADS CONSIDERED. PLEASE EXPLAIN OR PROVIDE A
 BRIEF NARRATIVE.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 7) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED.
 FLEXIBLE PIPING IS NOT INDICATED ON THE CALCULATIONS
 FOR REMOTE AREA # 2.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 8) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED. SHEET
 501 DOES NOT INDICATE SPECIFICATIONS FOR FLEXIBLE PIPE
 AND NO SPEC SHEETS ARE PROVIDED. PLEASE INDICATE ON
 SHEET 501 AND PROVIDE SPEC SHEETS.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 9) SHEET FP 120 B - COMPLIED WITH NEW SHEET, NO
 REVISION CLOUD PROVIDED.
  
 10) SHEET FP 160 A - COMPLIED WITH LETTER.
  
 11) SHEET FP 160 C - COMPLIED WITH NEW SHEET, NO
 REVISION CLOUD PROVIDED.
  
 12 ) SHEET FP 501 - COMPLIED WITH NEW PRESSURE TEST, NO
 REVISION CLOUD PROVIDED.
  
 13) SHEET FP 501 - NOTE # 1 - THERE IS NO TRANSFER
 SWITCH INDICATED ON THE CONTROLLER. EMERGENCY POWER IS
 REQUIRED AND SHALL BE PROVIDED. PROVIDE A TRANSFER
 SWITCH AND APPLICBALE SPEC SHEETS.
  
 APPEARS TO COMPLY, NO REVISON CLOUD PROVIDED.
  
 14) SHEET FP 501 - NOTE # 15 - A 175PSI REGUALTING
 VALVE IS INDICATED. NFPA 20 DOES NOT PERMIT FOR A
 REGULATING VALVE/DEVICE WITHIN THE FIRE PUMP SUCTION OR
 DISCHARGE PIPING. THE REGULATING VALVE/DEVICES ARE
 PERMITED BY NFPA 14 IN THE STANDPIPE SYSTEM. PLEASE
 CORRECT AND PROVIDE APPLICABLE SPECS FOR EACH FLOOR
 LOCATION
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 15) SHEET FP 501 - ROOF MANIFOLD DRAWINGS OR SPEC ARE
 NOT PROVIDED OR INDICATED. PLEASE PROVIDE.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
  
 PLEASE PROVIDE REVSION CLOUDS OR OTHER INDICATIONS ON
 EACH SHEET OF THE CHANGES MADE.
  
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL