2016-04-19 13:16:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET FP 110 A - THE SUBMITTED PLANS INDICATED AN
 ENGINEER'S STAMP THAT DOES NOT MATCH THE ENGINEER OF
 RECORD WHICH IS INCONSISTENT WITH FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15. THERE CAN BE ONLY
 ONE ENGINEER OF RECORD.
  
 2) SHEET FP 110 A - THE DESIGN SHOWS SEVERAL CHANGES
 FROM THE ORIGNAL ENGINNER OF RECORD SUBMITTAL. THE
 ENGINEER OF RECORD SHALL APPROVE BY STAMP OR LETTER THE
 SHOP DRAWINGS IN COMPLIANCE WITH FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15.
  
 3) SHEET FP 110 C - REMOTE AREA # 1 INDICATES
 0.100GPM/FT2 AND THE CLACULATIONS SHEETS INDICATES
 0.15GPM/FT2. PLEASE CORRECT AND CLARIFY WHICH IS
 CORRECT.
  
 4) SHEET FP 110 C - REMOTE AREA # 1 LAYOUT IS DIFFICULT
 TO DETERMINE AS THERE APPEARS TO BE TWO SETS OF BRANCH
 LINES IN THE SAME AREA. PLEASE CLARIFY OR SHOW
 ELEVATIONS.
  
 5) SHEET FP 110 C - PLEASE PROVIDE AND INDICATE EXACT
 DIMENSIONS AND SQUARE FOOTAGE OF ACTUAL REMOTE AREA #
 1. NO DIMENSIONS ARE INDICATED AND THE AREA IS NOT
 CLEARLY MARKED.
  
 6) SHEET FP 120 A - ALL THE ROOMS ARE NOT LABELED. ALL
 ROOMS SHALL BE LABELED OR INDICATED. THERE ARE TWO
 ROOMS WITH 1 SPRINKLER HEAD ONLY THAT APPEAR TO BE FOR
 ORDINARY HAZARD GROUP 1. WERE THE CALCULATION DEMANDS
 OF THESE HEADS CONSIDERED. PLEASE EXPLAIN OR PROVIDE A
 BRIEF NARRATIVE.
  
 7) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED.
 FLEXIBLE PIPING IS NOT INDICATED ON THE CALCULATIONS
 FOR REMOTE AREA # 2.
  
 8) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED. SHEET
 501 DOES NOT INDICATE SPECIFICATIONS FOR FLEXIBLE PIPE
 AND NO SPEC SHEETS ARE PROVIDED. PLEASE INDICATE ON
 SHEET 501 AND PROVIDE SPEC SHEETS.
  
 9) SHEET FP 120 B - THERE IS NO SHEET FP 120 B; A
 DUPLICATE SHEET FP 110 B IS IN ITS PLACE. PROVIDE
 PROPER SHEET.
  
 10) SHEET FP 160 A - A NOTE INDICATES REMOVED CANOPY
 FIRE PROTECTION. PLEASE PROVIDE EXPLANATION OR
 JUSTIFICATION FOR THIS NOTE WITH THE APPROVAL FROM THE
 ENGINEER OF RECORD.
  
 11) SHEET FP 160 C - THERE ARE TWO SHEETS INDICATED AS
 FP 160 C; SHEET FP 160 D IS MISSING. PLEASE PROVIDE
 CORRECT SHEET.
  
 12 ) SHEET FP 501 - A NOTE INDICATES A WATER FLOW TEST
 DATE OF 2014. PER NFPA 13, CHAPTER 22, 22.2 WATER
 SUPPLY INFORMATION, 22.2.1.1* WHERE A WATER FLOW TEST
 IS USED FOR THE PURPOSES OF SYSTEM DESIGN, THE TEST
 SHALL BE CONDUCTED NO MORE THAN 12 MONTHS PRIOR TO
 WORKING PLAN SUBMITTAL. PLEASE PROVIDE UPDATE
 INFORMATION.
  
 13) SHEET FP 501 - NOTE # 1 - THERE IS NO TRANSFER
 SWITCH INDICATED ON THE CONTROLLER. EMERGENCY POWER IS
 REQUIRED AND SHALL BE PROVIDED. PROVIDE A TRANSFER
 SWITCH AND APPLICBALE SPEC SHEETS.
  
 14) SHEET FP 501 - NOTE # 15 - A 175PSI REGUALTING
 VALVE IS INDICATED. NFPA 20 DOES NOT PERMIT FOR A
 REGULATING VALVE/DEVICE WITHIN THE FIRE PUMP SUCTION OR
 DISCHARGE PIPING. THE REGULATING VALVE/DEVICES ARE
 PERMITED BY NFPA 14 IN THE STANDPIPE SYSTEM. PLEASE
 CORRECT AND PROVIDE APPLICABLE SPECS FOR EACH FLOOR
 LOCATION
  
 15) SHEET FP 501 - ROOF MANIFOLD DRAWINGS OR SPEC ARE
 NOT PROVIDED OR INDICATED. PLEASE PROVIDE.
  
 16) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  