2016-04-27 19:14:47 | ELECTRICAL REVIEW COMMENTS |
| |
| CORRECTIONS REQUIRED: |
| 1. THERE ARE SEVERAL ITEMS THAT MAY NOT BE TO CODE BUT |
| WERE INITIALLY MISSED BY BOTH MYSELF AND LATER THE |
| INSPECTOR. |
| 2. PROVIDE MANUFACTURER SPECS FOR BOTH, THE RANGE/OVEN |
| AND HVAC TO CONFIRM THAT THE OCPD AND WIRING AS |
| INDICATED ON YOUR PANEL SCHEDULES IS ACCEPTABLE, |
| OTHERWISE CORRECT THE PANEL SCHEDULE AND LOAD CALCS |
| ACCORDINGLY. |
| 3. FBC-R303.9 REQUIRE THAT YOU PROVIDE HEAT ENOUGH TO |
| MAINTAIN 68 DEGREES WITHIN 3? OF THE FLOOR IN EVERY |
| HABITABLE ROOM. THE HVAC LOADS INDICATED DO NOT REFLECT |
| THAT. |
| 4. CORRECTION TO THE SMOKE DETECTOR NOTE. SMOKE |
| DETECTORS MAY NOT BE WITHIN 20? OF THE RANGE UNLESS IT |
| CAN BE SILENCED. |
| 5. IF ROOM 100 IS AN EXTERIOR ROOM IT BECOMES A PORCH |
| BY CODE STANDARDS AND AS PER NEC 210.52(E)(3), IT |
| REQUIRES AN OUTLET. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |