2016-04-27 19:14:47ELECTRICAL REVIEW COMMENTS
  
 CORRECTIONS REQUIRED:
 1. THERE ARE SEVERAL ITEMS THAT MAY NOT BE TO CODE BUT
 WERE INITIALLY MISSED BY BOTH MYSELF AND LATER THE
 INSPECTOR.
 2. PROVIDE MANUFACTURER SPECS FOR BOTH, THE RANGE/OVEN
 AND HVAC TO CONFIRM THAT THE OCPD AND WIRING AS
 INDICATED ON YOUR PANEL SCHEDULES IS ACCEPTABLE,
 OTHERWISE CORRECT THE PANEL SCHEDULE AND LOAD CALCS
 ACCORDINGLY.
 3. FBC-R303.9 REQUIRE THAT YOU PROVIDE HEAT ENOUGH TO
 MAINTAIN 68 DEGREES WITHIN 3? OF THE FLOOR IN EVERY
 HABITABLE ROOM. THE HVAC LOADS INDICATED DO NOT REFLECT
 THAT.
 4. CORRECTION TO THE SMOKE DETECTOR NOTE. SMOKE
 DETECTORS MAY NOT BE WITHIN 20? OF THE RANGE UNLESS IT
 CAN BE SILENCED.
 5. IF ROOM 100 IS AN EXTERIOR ROOM IT BECOMES A PORCH
 BY CODE STANDARDS AND AS PER NEC 210.52(E)(3), IT
 REQUIRES AN OUTLET.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  