2016-04-12 12:35:34ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 2010 FLORIDA BLDG. CODES; 2008 NEC
  
 CORRECTIONS REQUIRED FOR THE SUBMITTED AS-BUILT
 DRAWINGS AS INDICATED BELOW. WHERE THREE AND FOUR WAY
 SWITCHING IS MENTIONED PLEASE NOTE THAT THIS IS ONLY A
 SUGGESTION IN THE INTEREST OF ENERGY CONSERVATION, LIFE
 SAFETY AND USER CONVENIENCE AND THEY DO NOT HAVE TO BE
 INSTALLED.
 1. NEC 250.94 MISSING THE INTER SYSTEM BONDING TERMINAL
 REQUIRED.
 2. NEC 110.12 & NEC 408.4 THE AS-BUILT DRAWINGS PANEL
 SCHEDULES SHOULD INDICATE THE PANEL?S MANUFACTURER NAME
 BRAND.
 3. NEC 220 PART III ADJUST THE LOADS AND CALCS AS
 INSTRUCTED BY NEC. I WORKED THE LOAD CALCS AND CAME UP
 WITH A MUCH LOWER NUMBER.
 4. REVISE THE SWITCH SYMBOL ON THE DRAWINGS TO MATCH
 THE LEGEND
 5. NEC 210.70(A)(1) PROVIDE A WALL SWITCH FOR THE LIGHT
 IN ROOM 100.
 6. NEC 210.70(A)(1) PROVIDE THE REQUIRED LIGHT AND WALL
 SWITCH IN ROOMS 113, 105 & 109.
 7. NEC 210.52(A)(1) OUTLET SPACING IN ROOM 213 IS NOT
 TO CODE.
 8. NEC 210.70(A)(1) THERE SHALL BE A LIGHT CONTROLLED
 BY A WALL SWITCH IN THE ROOM BETWEEN ROOMS 211 & 213.
 PREFERABLY THIS LIGHT SHOULD HAVE A 3 WAY SWITCH.
 9. ADD AN ADDITIONAL SWITCH FOR THE HALL 201 AND
 VESTIBULE 211 AS IT EXITS INTO ROOM 213. THIS WOULD BE
 A 4 WAY SWITCH.
 10. NEC 210.52(E)(3) A GFI PROTECTED OUTLET IS REQUIRED
 IN THE BALCONY OUTSIDE OF ROOM 202.
 11. A 3 WAY SWITCH TO CONTROL HALL WAY 207 LIGHTS AS IT
 EXITS INTO ROOM 209 IS SUGGESTED.
 12. NEC 406.8 ALL RECEPTACLES IN DAMP OR WET LOCATIONS
 SHALL BE LISTED WEATHER-RESISTANT IN ADDITION TO HAVING
 AN IN-USE TYPE COVER.
 13. FBC-E SECTION 404.1 A MINIMUM OF 50% OF THE LAMPS
 IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER