Plan Review Notes For Permit 16040430 |
Permit Number |
16040430 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-11-16 06:56:37 | APPROVED WITH EXCEPTIONS | | BUILDING PROVISO | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | ENHANCED FASTENING CALCULATIONS FOR THE POLYGLASS | | MODIFIED ROOFING SYSTEM. (THE ROOF DESIGN UPLIFT | | PRESSURES ON SHEET S-3 SHOULD USE 10 SQUARE FT. RATHER | | THAN 20 SQUARE FOR THE EFFECTIVE WIND AREA WHICH | | RESULTS IN GREATER UPLIFT PRESSURES THAN THE ONES THAT | | ARE LISTED.) | | 2) SUBMIT TWO SETS DETAILS AND INSTALLATION | | INSTRUCTIONS FOR THE ELEVATOR SHAFT, THE ELEVATOR AND | | THE ELEVATOR EQUIPMENT. |
|