2016-11-16 06:56:37APPROVED WITH EXCEPTIONS
 BUILDING PROVISO
 1) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 ENHANCED FASTENING CALCULATIONS FOR THE POLYGLASS
 MODIFIED ROOFING SYSTEM. (THE ROOF DESIGN UPLIFT
 PRESSURES ON SHEET S-3 SHOULD USE 10 SQUARE FT. RATHER
 THAN 20 SQUARE FOR THE EFFECTIVE WIND AREA WHICH
 RESULTS IN GREATER UPLIFT PRESSURES THAN THE ONES THAT
 ARE LISTED.)
 2) SUBMIT TWO SETS DETAILS AND INSTALLATION
 INSTRUCTIONS FOR THE ELEVATOR SHAFT, THE ELEVATOR AND
 THE ELEVATOR EQUIPMENT.