Plan Review Notes
Plan Review Notes For Permit 16040430
Permit Number 16040430
Review Stop B
Sequence Number 3
Notes
Date Text
2016-10-20 18:14:09PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC R401.3 SURFACE WATER
 DRAINAGE ON THE SITE PLAN. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 WHERE LOT LINES, WALLS, SLOPES OR OTHER PHYSICAL
 BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL WITHIN 10
 FEET (3048 MM), DRAINS OR SWALES SHALL BE CONSTRUCTED
 TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. IMPERVIOUS
 SURFACES WITHIN 10 FEET (3048 MM) OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY
 FROM THE BUILDING. SUBMIT TWO COPIES OF A SURFACE WATER
 DRAINAGE PLAN THAT SHOWS THE FLOW OF THE SURFACE WATER.
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO
 MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO.
 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA. THE
 MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ASSEMBLIES LISTED IN THE PRODUCT APPROVAL ARE TYPICALLY
 FOR ROOF ZONE ONE AND REQUIRE ENHANCED FASTENING FOR
 THE PERIMETER (ZONE 2) AND CORNER ZONES(ROOF ZONE 3).
 PLEASE INDICATE THE APPROVED ASSEMBLY AND THE DESIGN
 PRESSURE FROM THE PRODUCT APPROVAL THAT WILL BE USED
 AND SUBMIT THE RAS 117 ENHANCED FASTENING CALCULATIONS.
  
 4) SPECIFY THE APPROVED ASSEMBLY AND THE DESIGN
 PRESSURES FOR THE TAMKO MODIFIED ROOFING SYSTEM OVER
 CONCRETE DECK THAT WILL BE USED. CIRCLE THE APPROPRIATE
 INFORMATION ON THE PRODUCT APPROVAL. FBC 107.2.1
  
 5) THIS WILL BE NOTED ON THE PLANS. ENGINEERED SHOP
 DRAWINGS FOR THE GLASS BALCONY GUARDS ARE REQUIRED TO
 BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. FBC
 R312, R308.4.4 & FBC107.3.4.2
  
  