2016-10-20 18:14:09 | PLAN |
| REVIEW COMMENTS |
| |
| 3RD REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SHOW COMPLIANCE WITH FBC R401.3 SURFACE WATER |
| DRAINAGE ON THE SITE PLAN. SURFACE DRAINAGE SHALL BE |
| DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED |
| POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS |
| SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). |
| WHERE LOT LINES, WALLS, SLOPES OR OTHER PHYSICAL |
| BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL WITHIN 10 |
| FEET (3048 MM), DRAINS OR SWALES SHALL BE CONSTRUCTED |
| TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. IMPERVIOUS |
| SURFACES WITHIN 10 FEET (3048 MM) OF THE BUILDING |
| FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY |
| FROM THE BUILDING. SUBMIT TWO COPIES OF A SURFACE WATER |
| DRAINAGE PLAN THAT SHOWS THE FLOW OF THE SURFACE WATER. |
| |
| 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO |
| MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO. |
| 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA. THE |
| MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| ASSEMBLIES LISTED IN THE PRODUCT APPROVAL ARE TYPICALLY |
| FOR ROOF ZONE ONE AND REQUIRE ENHANCED FASTENING FOR |
| THE PERIMETER (ZONE 2) AND CORNER ZONES(ROOF ZONE 3). |
| PLEASE INDICATE THE APPROVED ASSEMBLY AND THE DESIGN |
| PRESSURE FROM THE PRODUCT APPROVAL THAT WILL BE USED |
| AND SUBMIT THE RAS 117 ENHANCED FASTENING CALCULATIONS. |
| |
| 4) SPECIFY THE APPROVED ASSEMBLY AND THE DESIGN |
| PRESSURES FOR THE TAMKO MODIFIED ROOFING SYSTEM OVER |
| CONCRETE DECK THAT WILL BE USED. CIRCLE THE APPROPRIATE |
| INFORMATION ON THE PRODUCT APPROVAL. FBC 107.2.1 |
| |
| 5) THIS WILL BE NOTED ON THE PLANS. ENGINEERED SHOP |
| DRAWINGS FOR THE GLASS BALCONY GUARDS ARE REQUIRED TO |
| BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. FBC |
| R312, R308.4.4 & FBC107.3.4.2 |
| |
| |