Plan Review Notes For Permit 16040430 |
Permit Number |
16040430 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-07-23 12:03:07 | 1) SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS ARE | | REQUIRED PER 2014 FPC SEC. 1108. IF SCUPPERS ARE | | SUPPLIED, COMPLY WITH TABLE 1106.7 OF THE FPC. | | 2) WASHING MACHINE DRAIN IS UNDERSIZED & NOT VENTED. | | 2014 FBCR SEC. P3201.7, P3101.2. | | 3) SHOWER IN CABANA BATH NOT PROPERLY VENTED. 2014 FBCR | | SEC. P3201.7, P3101.2. | | 4) SHOWER IN HIS BATH NOT PROPERLY VENTED. 2014 FBCR | | SEC. P3201.7, P3101.2. | | 5) WET VENT FOR HER BATH IS UNDERSIZED. 2014 FBCR SEC. | | P3108.3. | | 6) SIZE ALL VENTS ON THE SANITARY RISER. | | 7) SINK IN SUMMER KITCHEN NOT ON SANITARY RISER. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|