Plan Review Notes
Plan Review Notes For Permit 16040430
Permit Number 16040430
Review Stop B
Sequence Number 2
Notes
Date Text
2016-08-04 19:12:16PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA ( A5 ). THE MINIMUM FINISH FLOOR ELEVATION
 INCLUDING THE 6" FREE BOARD REQUIRED BY THE CITY OF
 WEST PALM BEACH IS 7.5' NGVD. THE GARAGE FLOOR AND THE
 EQUIPMENT PADS ARE ALSO REQUIRED TO BE AT OR ABOVE 7.5'
 NGVD. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS ON
 THE PLANS. FBC-R 322.1 THE ELEVATIONS OF THE ATTACHED
 GARAGE AND THE EQUIPMENT PADS WERE NOT SPECIFIED ON THE
 PLANS.
  
 2) SHOW COMPLIANCE WITH FBC R401.3 SURFACE WATER
 DRAINAGE ON THE SITE PLAN. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 3) PROVIDE STRUCTURAL AND FASTENING DETAILS FOR THE
 STEEL ANGLE LEDGE THAT WILL BE USED TO SUPPORT THE
 STONE WALL VENEER. FBC R703.7.2.1 & R703.7.2.2
  
 4) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO
 MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO.
 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE ROOFING SYSTEM THAT
 WILL BE USED OVER THE CONCRETE DECKS. DCA RULE 9N-3 THE
 PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 6) THE PRODUCT APPROVALS FOR THE TAMKO ROOFING SYSTEMS
 HAVE SEVERAL DIFFERENT APPROVED ASSEMBLIES WITH
 DIFFERENT DESIGN PRESSURES, SPECIFY THE ASSEMBLY AND
 THE DESIGN PRESSURES THAT WILL BE INSTALLED. IF THE
 PRODUCT'S DESIGN PRESSURES ARE NOT ADEQUATE FOR THE
 INCREASED PRESSURES AT THE PERIMETER AND CORNER AREAS,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED TO BE SUBMITTED IN ACCORDANCE WITH LIMITATION
 #7 ON THE LAST PAGE OF THE NOA.
  
 7) SUBMIT ENGINEERED SHOP DRAWINGS FOR THE GLASS
 BALCONY GUARDS FOR REVIEW PRIOR TO INSTALLATION. FBC
 R312, R308.4.4 & FBC107.3.4.2
  
  
  
  