Plan Review Notes
Plan Review Notes For Permit 16040430
Permit Number 16040430
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-14 15:51:491ST ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. ISSUES ON THE ELECTRICAL NOTES OF PAGES E-1 & E-2
 A) NOTE 2, STATES THE CURRENT CODE. YOU SHALL INDICATE
 THE ACTUAL CODE TO WHICH THE PROJECT IS DESIGNED. IN
 THIS CASE THE APPLICABLE ELECTRICAL CODE IS THE 2011
 EDITION OF THE NEC.
 B) NOTE 7, THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO
 IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT
 A TYPE OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR
 ?NMS?.
 C) NOTE 8, AS ABOVE, THE APPLICABLE CODE IS NOT THE
 LATEST, BUT THE 2011 EDITION.
 2. NEC 404.4. WHERE SWITCHES CONTROLLING LIGHTING LOADS
 SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE GROUNDED
 BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING
 CIRCUIT SHALL BE PROVIDED AT THE SWITCH.
 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 4. SHOW HVAC EQUIPMENT AND ITS RESPECTIVE DISCONNECT ON
 THE ELECTRICAL FLOOR PLANS.
 5. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY. AN
 OUTLET IS REQUIRED WITHIN THE PERIMETER OF THE SUN
 DECK.
 6. THE SUBMITTED RISER DIAGRAM HAS PANELS A, B, C &
 POOL PANEL. PANELS ARE NOT IDENTIFIED ON THE ELECTRICAL
 FLOOR PLAN. SHOW ALL PANELS ON THE ELECTRICAL FLOOR
 PLANS.
 7. NEC 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE
 TWO TO SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE
 GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED.
 8. THE POOL EQUIPMENT SHALL BE IDENTIFIED IF IT IS A
 PART OF THE SCOPE, OTHERWISE MARK IT AS FUTURE.
 9. EVERY ROOM ON THE FLOOR PLAN SHALL BE LABELED TO
 ASCERTAIN MINIMUM ELECTRICAL REQUIREMENTS IF
 APPLICABLE.
 10. NEC 310.15(B)(7) PERMITS #3 CU FOR 110 AMP
 RESIDENTIAL SERVICES. PANELS ?C? & POOL ARE SAID TO BE
 100 AMP ON THE LABEL YET THE SPECS INDICATE A 200 AMP
 BUS RATING AND MAIN BREAKER FED WITH 3 #3AWG. CORRECT
 ACCORDINGLY.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  