2016-04-14 15:51:49 | 1ST ELECTRICAL REVIEW COMMENTS |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| EDITION |
| |
| CORRECTIONS REQUIRED: |
| 1. ISSUES ON THE ELECTRICAL NOTES OF PAGES E-1 & E-2 |
| A) NOTE 2, STATES THE CURRENT CODE. YOU SHALL INDICATE |
| THE ACTUAL CODE TO WHICH THE PROJECT IS DESIGNED. IN |
| THIS CASE THE APPLICABLE ELECTRICAL CODE IS THE 2011 |
| EDITION OF THE NEC. |
| B) NOTE 7, THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO |
| IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT |
| A TYPE OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR |
| ?NMS?. |
| C) NOTE 8, AS ABOVE, THE APPLICABLE CODE IS NOT THE |
| LATEST, BUT THE 2011 EDITION. |
| 2. NEC 404.4. WHERE SWITCHES CONTROLLING LIGHTING LOADS |
| SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE GROUNDED |
| BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING |
| CIRCUIT SHALL BE PROVIDED AT THE SWITCH. |
| 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| PADDLE FANS HEAVIER THAN 70 LBS. |
| 4. SHOW HVAC EQUIPMENT AND ITS RESPECTIVE DISCONNECT ON |
| THE ELECTRICAL FLOOR PLANS. |
| 5. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN |
| 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| INSTALLED WITHIN THE PERIMETER OF THE BALCONY. AN |
| OUTLET IS REQUIRED WITHIN THE PERIMETER OF THE SUN |
| DECK. |
| 6. THE SUBMITTED RISER DIAGRAM HAS PANELS A, B, C & |
| POOL PANEL. PANELS ARE NOT IDENTIFIED ON THE ELECTRICAL |
| FLOOR PLAN. SHOW ALL PANELS ON THE ELECTRICAL FLOOR |
| PLANS. |
| 7. NEC 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE |
| TWO TO SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE |
| GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE |
| THE LOAD SERVED. |
| 8. THE POOL EQUIPMENT SHALL BE IDENTIFIED IF IT IS A |
| PART OF THE SCOPE, OTHERWISE MARK IT AS FUTURE. |
| 9. EVERY ROOM ON THE FLOOR PLAN SHALL BE LABELED TO |
| ASCERTAIN MINIMUM ELECTRICAL REQUIREMENTS IF |
| APPLICABLE. |
| 10. NEC 310.15(B)(7) PERMITS #3 CU FOR 110 AMP |
| RESIDENTIAL SERVICES. PANELS ?C? & POOL ARE SAID TO BE |
| 100 AMP ON THE LABEL YET THE SPECS INDICATE A 200 AMP |
| BUS RATING AND MAIN BREAKER FED WITH 3 #3AWG. CORRECT |
| ACCORDINGLY. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |