2016-05-16 16:46:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA ( A5 ). THE MINIMUM FINISH FLOOR ELEVATION
 INCLUDING THE 6" FREE BOARD REQUIRED BY THE CITY OF
 WEST PALM BEACH IS 7.5' NGVD. THE GARAGE FLOOR AND THE
 EQUIPMENT PADS ARE ALSO REQUIRED TO BE AT OR ABOVE 7.5'
 NGVD. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS ON
 THE PLANS. FBC-R 322.1
  
 2) SUBMIT TWO SETS OF A PRE-CONSTRUCTION ELEVATION
 CERTIFICATE THAT SHOWS COMPLIANCE WITH THE CITY'S FLOOD
 ORDINANCE.
  
 3) SUBMIT TWO SETS OF A SIGNED AND SEALED SUB-SURFACE
 SOIL INVESTIGATION REPORT. FBC-R401.4
  
 4) SUBMIT TWO SETS OF A SURVEY/SITE PLAN THAT SHOWS THE
 LOCATION OF THE PROPOSED STRUCTURES AND THE DISTANCES
 TO PROPERTY LINES. FBC-R302.1
  
 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY COMPLIANCE FORM R405. FBC ENERGY R103.1.1.2
  
 6) SHOW COMPLIANCE WITH FBC-R302.1.2 DRAFTSTOPPING. THE
 CONCEALED SPACE IN THE FLOOR/CEILING ASSEMBLY BETWEEN
 THE FIRST AND SECOND FLOOR CAN NOT EXCEED 1,000 SQUARE
 FEET AND IS REQUIRED TO BE DIVIDED INTO TWO
 APPROXIMATELY EQUAL AREAS.
  
 7) THE FIRST FLOOR PLAN ON SHEET A-2 SPECIFIES A
 BEDROOM NUMBER 4 AND IT APPEARS THAT THIS DWELLING ONLY
 HAS 3 BED ROOMS. THE STUDY/EXERCISE ROOM DOES NOT HAVE
 A CLOSET AND IS NOT CONSIDERED A BEDROOM. FBC 107.2.1
  
 8) ON SHEET A-2 THE ENGINEERING CRITERIA HAS THE
 OCCUPANCY TYPE AS R2 AND SINGLE FAMILY DWELLINGS ARE
 R3.
  
 9) THE FOUNDATION NOTES ON S-1 LIST THE WRONG EDITIONS
 OF THE REFERENCE STANDARDS. THESE ARE THE CORRECT ONES:
 ACI 530/530.1-11, ASCE 5-11 AND ASCE 6-11. FBC-R
 CHAPTER 46
  
 10) THE NOTES ON A-1 LIST THE WRONG EDITIONS OF THE
 REFERENCE STANDARDS. THESE ARE THE CORRECT ONES: ASTM
 C94-09, ACI 318-11, ACI 332-10, ACI 53-11 AND ACI
 530.1-11. FBC-R CHAPTER 46
  
 11) ON SHEET A-8 THE ROOF NOTE FOR WOOD FRAMING AND THE
 PLYWOOD DECKING HAS AN ARROW THAT POINTS TO THE
 CONCRETE DECK. FBC 107.2.1
  
 12) SUBMIT PRODUCT APPROVALS FOR THE STONE WALL VENEER.
 DCA RULE 9N-3
  
 13) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO
 MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO.
 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE ROOFING SYSTEM
 THAT WILL BE USED OVER THE CONCRETE DECKS. DCA RULE
 9N-3
  
  
  
  
  
  