2016-05-16 16:46:01 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA ( A5 ). THE MINIMUM FINISH FLOOR ELEVATION |
| INCLUDING THE 6" FREE BOARD REQUIRED BY THE CITY OF |
| WEST PALM BEACH IS 7.5' NGVD. THE GARAGE FLOOR AND THE |
| EQUIPMENT PADS ARE ALSO REQUIRED TO BE AT OR ABOVE 7.5' |
| NGVD. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS ON |
| THE PLANS. FBC-R 322.1 |
| |
| 2) SUBMIT TWO SETS OF A PRE-CONSTRUCTION ELEVATION |
| CERTIFICATE THAT SHOWS COMPLIANCE WITH THE CITY'S FLOOD |
| ORDINANCE. |
| |
| 3) SUBMIT TWO SETS OF A SIGNED AND SEALED SUB-SURFACE |
| SOIL INVESTIGATION REPORT. FBC-R401.4 |
| |
| 4) SUBMIT TWO SETS OF A SURVEY/SITE PLAN THAT SHOWS THE |
| LOCATION OF THE PROPOSED STRUCTURES AND THE DISTANCES |
| TO PROPERTY LINES. FBC-R302.1 |
| |
| 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| ENERGY COMPLIANCE FORM R405. FBC ENERGY R103.1.1.2 |
| |
| 6) SHOW COMPLIANCE WITH FBC-R302.1.2 DRAFTSTOPPING. THE |
| CONCEALED SPACE IN THE FLOOR/CEILING ASSEMBLY BETWEEN |
| THE FIRST AND SECOND FLOOR CAN NOT EXCEED 1,000 SQUARE |
| FEET AND IS REQUIRED TO BE DIVIDED INTO TWO |
| APPROXIMATELY EQUAL AREAS. |
| |
| 7) THE FIRST FLOOR PLAN ON SHEET A-2 SPECIFIES A |
| BEDROOM NUMBER 4 AND IT APPEARS THAT THIS DWELLING ONLY |
| HAS 3 BED ROOMS. THE STUDY/EXERCISE ROOM DOES NOT HAVE |
| A CLOSET AND IS NOT CONSIDERED A BEDROOM. FBC 107.2.1 |
| |
| 8) ON SHEET A-2 THE ENGINEERING CRITERIA HAS THE |
| OCCUPANCY TYPE AS R2 AND SINGLE FAMILY DWELLINGS ARE |
| R3. |
| |
| 9) THE FOUNDATION NOTES ON S-1 LIST THE WRONG EDITIONS |
| OF THE REFERENCE STANDARDS. THESE ARE THE CORRECT ONES: |
| ACI 530/530.1-11, ASCE 5-11 AND ASCE 6-11. FBC-R |
| CHAPTER 46 |
| |
| 10) THE NOTES ON A-1 LIST THE WRONG EDITIONS OF THE |
| REFERENCE STANDARDS. THESE ARE THE CORRECT ONES: ASTM |
| C94-09, ACI 318-11, ACI 332-10, ACI 53-11 AND ACI |
| 530.1-11. FBC-R CHAPTER 46 |
| |
| 11) ON SHEET A-8 THE ROOF NOTE FOR WOOD FRAMING AND THE |
| PLYWOOD DECKING HAS AN ARROW THAT POINTS TO THE |
| CONCRETE DECK. FBC 107.2.1 |
| |
| 12) SUBMIT PRODUCT APPROVALS FOR THE STONE WALL VENEER. |
| DCA RULE 9N-3 |
| |
| 13) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO |
| MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO. |
| 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA. |
| |
| 14) SUBMIT PRODUCT APPROVALS FOR THE ROOFING SYSTEM |
| THAT WILL BE USED OVER THE CONCRETE DECKS. DCA RULE |
| 9N-3 |
| |
| |
| |
| |
| |
| |