2017-01-05 10:57:354TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16040412
 1/5/17
  
 1) THE ENERGYGAUGE COMPLIANCE FORM IS INDICATING 17
 SEER FOR RTU'S 5-9, HOWEVER THE EQUIPMENT SCHEDULE ON
 THE PLANS LISTS THEM AT 13 SEER- PLEASE CORRECT.
  
 2) PROVIDE COMPLIANCE DATA ON THE ENERGYGAUGE FORM FOR
 OAU-1.
  
 2) AUTOMATIC SHUTOFF DAMPERS ARE REQUIRED FOR THE OAU
 DUCTS SUPPLYING THE RTU'S- SEE SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 3) PREVIOUS COMMENT #9 STILL EXISTS: PROVIDE A FIRE
 DAMPER FOR THE 8X6 O/A DUCT PENETRATING THE THE
 FIRE-RATED PD RECORDS WALL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER