Plan Review Notes
Plan Review Notes For Permit 16040412
Permit Number 16040412
Review Stop M
Sequence Number 3
Notes
Date Text
2016-12-02 10:48:563RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16040415
 12/2/16
  
 1) SHEETS M-1 & M-2.1: IT APPEARS THAT THE RTU
 SCHEDULE, AND THE ENERGY AND AC CALCULATIONS ARE
 INDICATING NEW UNITS ARE BEING INSTALLED. PLEASE
 CORRECT THE MECHANICAL ROOF PLAN INDICATING EXISTING.
  
 2) CLARIFY IF THE DUCT HEATERS ARE NEW OR EXISTING AND
 LABEL THEM ACCORDINGLY. IF NEW UNITS ARE BEING
 PROVIDED, PLEASE PROVIDE AN EQUIPMENT SCHEDULE.
  
 3) M-1, FAN SCHEDULE: PROVIDE THE CONTROL SEQUENCE FOR
 EF-7.
  
 4) M-1 & M-2.0A: THE EXHAUST CALCULATION IS SPECIFYING
 EXHAUST RATES BASED ON SECTION 502.8.1.1 FBC-14
 MECHANICAL. PLEASE REVIEW AND SHOW COMPLIANCE WITH
 ITEMS #1-7 UNDER 502.8.1.1, AND ALSO REFER TO SECTION
 510.8 FOR EXHAUST DUCT REQUIREMENTS AND SHOW DETAILS ON
 THE PLAN.
  
 5) PLEASE REFER TO TABLE 7-1 ASHRAE 170- 2008 AND
 PROVIDE THE DESIGN PARAMETERS FOR THE SOILED UITILITY
 AND MEDICAL WASTE ROOMS. SHOW PRESSURE RELATIONSHIPS
 AND REQUIRED OUTDOOR AND TOTAL AIR CHANGES RO EACH
 ROOM.
  
 6) PROVIDE AIR BALANCE CALCULATIONS THAT INCLUDE THE
 NEW EXHAUST VENTILATION SYSTEMS.
  
 7) 2ND REQUEST FOR THE DEFINITION OF "HT" STORAGE ROOM
 AND WHAT MATERIALS ARE BEING STORED IN THE ROOM. AS
 PREVIOUSLY NOTED EXHAUST VENTILATION MAY BE REQUIRED
 AND RECIRCULATION IOF AIR PROHIBITED.
  
 8) M2.0A: SHOW THE DUCT DROP AND DUCT PLAN FOR OAU-1.
  
 9) M2.0A: THERE APPEARS TO BE A MISSING FIRE DAMPER
 WHERE THE 8X6 DUCT IS PENETRATING THE FIRE-RATED PD
 RECORDS ROOM WALL.
  
 10 ) A RESPONSE NARRATIVE WAS NOT SUBMITTED WITH THE
 CORRECTED PLANS. PLEASE PROVIDE A RESPONSE NARRATIVE
 ADDRESSING THESE REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER