2016-12-14 15:48:17JOB PERMIT NUMBER: 1640412 & 16040415
 JOB ADDRESS: 1600 & 1522 N DIXIE HWY
 WEST PALM BEACH FLORIDA 33401
 DATE: DECEMBER 14, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] BUILDING 1600 N DIXIE HIGHWAY RISER DIAGRAM REFLECTS
 THE EQUIPMENT GROUNDING CONDUCTOR FOR PANEL "DP" IN
 PARALLEL WHICH IS IN VIOLATION OF NEC 310.10(H) &
 250.122(F).
  
 2] BY MODIFICATIONS DONE TO THE ELECTRICAL SYSTEM,
 USING THE EXISTING AVAILABLE FAULT CURRENT PLEASE SHOW
 AIC CALCULATIONS TO VERIFY SHORT CIRCUIT RATING OF NEW
 ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9.
  
 3] IN ADDITION TO THE SERVICE PERMANENT PLAQUE REQUIRED
 BY NEC 230.2(E) PLEASE PROVIDE A SHUNT TRIP DEVICE AT
 EACH SERVICE LOCATION TO FACILITATE FIRST RESPONDERS,
 THE DEVICE SHALL BE INSTALLED AT A READILY ACCESSIBLE
 LOCATION PER NEC 230.70(A)(3).
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 3RD REVIEW FBC 2014 5TH ED. NEC 2011