2016-08-04 14:44:28 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #16040412 |
| 8/4/16 |
| |
| 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW: A) |
| PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE SOILED |
| UTILITY, MED WASTE, AND LAB ROOMS. B) PROVIDE AN |
| EXHAUST SYSTEM IN THE LAB ROOM PER TABLE 403.3 AND |
| ASHRAE 62.1-2010. PLEASE NOTE THAT RECIRCULATION OF AIR |
| FROM THE SPACE IS PROHIBITED PER TABLE 403.3 FOOTNOTE G |
| |
| 2) DEFINE "HT" AS IT APPLIES TO THE HT STORAGE ROOM. |
| INDICATE WHAT MATERIALS AND/OR EQUIPMENT ARE BEING |
| STORED IN THE ROOM. PLEASE NOTE THAT EXHAUST |
| VENTILATIONS MAY BE REQUIRED. |
| |
| 3) M-3.1: AS PREVIOUSLY REQUESTED PROVIDE COMPLETE |
| ENGINEERED DETAILS FOR MOUNTING THE NEW RTU'S TO THE |
| CURBS- SECTION 301.15. PLEASE INCLUDE THE WIND LOAD |
| DESIGN CRITERIA FOR THE INSTALLATIONS AS OUTLINED IN |
| SECTION 1609 FBC-14 BUILDING. CONTRARY TO THE RESPONSE |
| NARRATIVE FROM JMM ENGINEERS, RTU'S 5, 6, 7, 8, &9 ARE |
| NOT EXISTING AND WERE NEVER PERMITTED. BUILDING |
| DEPARTMENT RECORDS INDICATE PERMIT #15070429 WAS ISSUED |
| FOR INSTALLATION OF THE CURBS ONLY WITH CAPPING FOR |
| FUTURE USE. WIND LOAD ENGINEERING IS ALSO REQUIRED |
| INSTALLATION OF THE ROOFTOP FANS AND CURBS- EF-1, 2, 3, |
| 4, 5, & 6. |
| |
| 4) SHEET M-2.1: AS PREVIOSULY REQUESTED, PROVIDE THE |
| CLEARANCE DISTANCE MEASURERMENTS FROM THE EXHAUST FANS |
| TO THE ROOF EDGES. ARE THERE PARAPETS THAT EXTEND AT |
| LEAST 42" ABOVE THE FINISHED ROOF SURFACE? |
| |