Plan Review Notes
Plan Review Notes For Permit 16040412
Permit Number 16040412
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-04 10:28:34ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: FRESENIUS MEDICAL CARE ADDITION
 JOB ADDRESS: 1522 & 1600 N. DIXIE HWY.
 DESCRIPTION: RENOVATION OF EXISTING SPACE
 MASTER PERMIT:16040415
 REVISION: (THIS PACKET IS RUNNING TOGETHER WITH PERMIT
 16040412)
  
 THE BELOW MENTIONED COMMENTS WILL RELATE TO BOTH
 PERMITS AS THEY ARE SHARING A SUBMITTAL
 1. THERE ARE TWO SEPARATE PERMITS AND THEREFORE THERE
 SHOULD BE TWO SEPARATE PLAN SETS. IF NOT AT A MINIMUM
 THREE SETS SO THAT ONE CAN BE STORED ON RECORD FOR EACH
 PERMIT NUMBER EVEN IF THEY WILL BE SHARING THE JOB
 COPY. AT PRESENT THERE IS ONLY ONE SET OF DRAWINGS
 ATTACHED TO EACH PERMIT AND THEY DO NOT MATCH. THE
 SHEET INDEX OF T1.0 FOR EACH SET MENTIONS 11
 INDIVIDUALLY NUMBERED ELECTRICAL SHEETS. THE SET OF
 PERMIT 16040415 IS MISSING SHEET E2.0A AND SHEET E2.2
 IS REPLACED W/SHEET E2.2A. THE SET OF PERMIT 16040412
 DOES INCLUDE SHEET E2.0A BUT ALSO HAS A SHEET E2.2A
 RATHER THAN AN E2.2. CORRECT THAT ACCORDINGLY.
 2. YOU DID NOT RESPOND TO MY COMMENT #3 WHICH ADDRESSES
 THE DAYLIGHT ZONE ISSUE. I INADVERTENTLY CALLED OUT
 SHEET E2.1 WHICH OBVIOUSLY DOES NOT INCLUDE THE
 LIGHTING. IT IS SHEET E2.0A THAT ADDRESSES THE LIGHTING
 AND NOTHING HAS BEEN DONE TO ADDRESS THE DAYLIGHT
 LIGHTING ZONE CONTROL. PLEASE CORRECT THAT ACCORDINGLY.
 3. WITH REGARDS TO MY COMMENT #4, THE FACT THAT THESE
 TWO BUILDINGS ARE TO BE CONNECTED WILL POSE A LIFE
 SAFETY HAZARD BY HAVING TWO SERVICES. THEREFORE, RATHER
 THAN HAVING SHUNT TRIP CAPABILITIES YOU SHALL PLACE A
 WARNING PLACARD AT EACH SERVICE INFORMING EMERGENCY
 PERSONNEL OF THE OTHER SERVICE AND THE LOCATION OF THE
 DISCONNECT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved