Date |
Text |
2016-08-04 10:28:34 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: FRESENIUS MEDICAL CARE ADDITION |
| JOB ADDRESS: 1522 & 1600 N. DIXIE HWY. |
| DESCRIPTION: RENOVATION OF EXISTING SPACE |
| MASTER PERMIT:16040415 |
| REVISION: (THIS PACKET IS RUNNING TOGETHER WITH PERMIT |
| 16040412) |
| |
| THE BELOW MENTIONED COMMENTS WILL RELATE TO BOTH |
| PERMITS AS THEY ARE SHARING A SUBMITTAL |
| 1. THERE ARE TWO SEPARATE PERMITS AND THEREFORE THERE |
| SHOULD BE TWO SEPARATE PLAN SETS. IF NOT AT A MINIMUM |
| THREE SETS SO THAT ONE CAN BE STORED ON RECORD FOR EACH |
| PERMIT NUMBER EVEN IF THEY WILL BE SHARING THE JOB |
| COPY. AT PRESENT THERE IS ONLY ONE SET OF DRAWINGS |
| ATTACHED TO EACH PERMIT AND THEY DO NOT MATCH. THE |
| SHEET INDEX OF T1.0 FOR EACH SET MENTIONS 11 |
| INDIVIDUALLY NUMBERED ELECTRICAL SHEETS. THE SET OF |
| PERMIT 16040415 IS MISSING SHEET E2.0A AND SHEET E2.2 |
| IS REPLACED W/SHEET E2.2A. THE SET OF PERMIT 16040412 |
| DOES INCLUDE SHEET E2.0A BUT ALSO HAS A SHEET E2.2A |
| RATHER THAN AN E2.2. CORRECT THAT ACCORDINGLY. |
| 2. YOU DID NOT RESPOND TO MY COMMENT #3 WHICH ADDRESSES |
| THE DAYLIGHT ZONE ISSUE. I INADVERTENTLY CALLED OUT |
| SHEET E2.1 WHICH OBVIOUSLY DOES NOT INCLUDE THE |
| LIGHTING. IT IS SHEET E2.0A THAT ADDRESSES THE LIGHTING |
| AND NOTHING HAS BEEN DONE TO ADDRESS THE DAYLIGHT |
| LIGHTING ZONE CONTROL. PLEASE CORRECT THAT ACCORDINGLY. |
| 3. WITH REGARDS TO MY COMMENT #4, THE FACT THAT THESE |
| TWO BUILDINGS ARE TO BE CONNECTED WILL POSE A LIFE |
| SAFETY HAZARD BY HAVING TWO SERVICES. THEREFORE, RATHER |
| THAN HAVING SHUNT TRIP CAPABILITIES YOU SHALL PLACE A |
| WARNING PLACARD AT EACH SERVICE INFORMING EMERGENCY |
| PERSONNEL OF THE OTHER SERVICE AND THE LOCATION OF THE |
| DISCONNECT. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |