Plan Review Notes
Plan Review Notes For Permit 16040412
Permit Number 16040412
Review Stop Z
Sequence Number 1
Notes
Date Text
2016-05-24 14:58:22FAILED
  
 1) PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE
 NOTE THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY
 RESULT IN ADDITIONAL COMMENTS
  
 2) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR
 OLD, WHICH SHOWS ALL IMPROVEMENTS AND EASEMENTS.
  
 3) THE CONNECTION BETWEEN THE TWO BUILDINGS EXTENDS
 INTO THE REQUIRED FIVE (5) FOOT SIDE SETBACK, WHICH IS
 NOT PERMITTED. IN ORDER TO CONNECT THE TWO BUILDINGS, A
 RECORDED UNITY OF TITLE IS REQUIRED TO REMOVE THE
 REQUIRED SETBACK ALONG WHAT IS CURRENTLY THE SHARED
 PROPERTY LINE. PLEASE CONTACT VINCE NOEL, CITY
 SURVEYOR, AT (561) 494-1096 TO BEGIN THE CITY'S UNITY
 OF TITLE APPLICATION PROCESS.
  
 4) THE PERMIT PACKAGE INCLUDES A PROPOSED SITE PLAN
 THAT RECONFIGURES THE EXISTING PARKING LOT AND JOINS IT
 WITH THE PARKING LOT TO THE SOUTH. IN ORDER TO VERIFY
 THAT THE NEW ENLARGED PARKING LOT HAS SUFFICIENT
 PARKING TO ACCOMMODATE BOTH THIS BUILDING AND THE
 BUILDING TO THE NORTH, A PARKING LOT PERMIT, WITH
 PLANS, SHALL BE SUBMITTED FOR REVIEW PRIOR TO STAFF?S
 APPROVAL OF THIS BUILDING PERMIT. NOTE: THE PROPOSED
 PARKING SPACES, REGULAR AND ADA, LOCATED ALONG THE EAST
 SIDE OF THE BUILDING WILL NOT FUNCTION AS SHOWN DUE TO
 THE DOORWAYS THAT ARE SHOWN ON THE PROPOSED FLOOR PLAN.
  
 5) IN ACCORDANCE WITH THE PROVISOS APPROVED AS PART OF
 PERMIT NO. 15100589, THE CURBING AND STRIPING SHOWN ON
 THE ISSUED PARKING LOT PERMIT SHALL BE COMPLETED PRIOR
 TO THE FINAL (104) INSPECTION/CERTIFICATE OF COMPLETION
 OF THE VANILLA BOX PERMIT OR CERTIFICATE OF OCCUPANCY
 FOR THE SPACE, WHICHEVER FIRST OCCURS.
  
 6) THE VALUE OF THE CONSTRUCTION ($241,020) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($339,394) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. SINCE THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY. THE
 LANDSCAPE WORK SHALL BE COMPLETED PRIOR TO A
 CERTIFICATE OF OCCUPANCY FOR THE BUILDING.
  
 7) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE
 POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL
 IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH
 POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION
 MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE.
  
 8) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
 E. AWNINGS
  
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  