2016-04-14 13:57:231ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040412
 4/14/16
  
 1) SHEET M1.0: THE OUTSIDE AIR CALULATIONS ARE BASED ON
 THE OUTDATED FMC- 2010. THE CURRENT CODE IN EFFECT IS
 THE FBC- 2014 MECHANICAL: PLEASE REVIEW AND UPDATE.
 2) M1.0: PLEASE INDICATE THE OFFICE OR ROOM NUMBERS IN
 THE OUTSIDE AIR SCHEDULE AND INCLUDE CALULATIONS FOR
 ALL ROOMS AND SPACES INCLUDING THE EXAMINATION AND
 MEDICAL PROCEDURE ROOMS- SEE TABLE 403.3. PLEASE NOTE
 THAT THE "WATER TREATMENT STORAGE" ROOMS LISTED IN THE
 CALCULATIONS DO NOT APPEAR TO BE IN THE SCOPE OF WORK
 FOR THIS PROJECT: PLEASE CLARIFY.
 3) M1.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE SOILED UTILITY, MED WASTE, AND LAB PREP ROOMS.
 PLEASE NOTE THAT NO EXHAUST HAS BEEN PROVIDED FOR THE
 LAB PREP ROOM- SEE TABLE 403.3 AND CLARIFY IF THERE IS
 LAB WORK OR CHEMICAL STORAGE IN THE THIS ROOM- SEE
 TABLE 6-4 ASHRAE 62.1-2010.
 4) D1.0: PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL
 DEMOLITION WITH CORREPONDING DRAWINGS AND DETAILS.
 5) M-2.0A: THE 10" FLEX DUCTS SUPPLYING 405 CFMS EACH
 TO THE CONFERENCE ROOM ARE UNDERSIZED PER ACCA MANUAL D
 SIZING METHODS FOR LOW PRESSURE SYSTEMS.
 6) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOF TOP EQUIPMENT- RTU'S, EXHAUST FANS, AIR
 INTAKES ETC- SEE SECTIONS 401.5 AND 501.3.1 FOR
 REQUIRED CLEARANCE DISTANCES AND PLACE MEASUREMENTS ON
 THE PLAN TO VERIFY COMPLIANCE. SUBMIT NOA'S OR FL.
 PRODUCT APPROVALS FOR THE ROOF TOP FANS, AND FAN AND
 RTU CURBS REVIEWED AND APPROVED WITH SIGNATURE BY THE
 EOR. PLEASE NOTE THAT GUARDS WILL BE REQUIRED FOR ALL
 SERVICEABLE EQUIPMENT ON THE ROOF WITHIN 10' OF A ROOF
 EDGE I.E. EF-6.
 7) INDICATE THE USE OF EF-6 ON THE PLAN AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS, MAKE-UP AIR, A
 VENTING DIAGRAM, AND MANUFACTURER'S SPECIFICATIONS FOR
 THE EXHAUST FAN AND DUCT WORK.
 8) M-3.1: REFER TO SECTION 301.15 AND PROVIDE WIND LOAD
 DESIGN CRITERIA AND COMPLETE ENGINEERED DETAILS FOR TIE
 DOWN OF THE RTUS, FANS, AND CURBS TO THE ROOF
 STRUCTURE.
  