Plan Review Notes
Plan Review Notes For Permit 16040412
Permit Number 16040412
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-13 18:52:32THIS PERMIT IS RIDING ALONG WITH16040415 AND ARE
 SHARING THE PLANS, THEREFORE THE COMMENTS ARE COMMON TO
 BOTH PERMIT.
  
 ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 BLDG. DEPT. NOTES ON COVER SHEET
 1. A) INDICATE THAT THE PLANS WERE DESIGNED TO MEET THE
 REQUIREMENTS OF THE 2008 NEC. D) REFERS TO THE LATEST
 CODE. THE 2011 EDITION OF THE NEC IS THE ONE CURRENTLY
 ADOPTED BUT IT IS NOT THE LATEST EDITION.
 SHEET E2.0A
 1. NOTE 14 AGAIN REFERS TO AN OLD CODE. THOUGH THE
 VERBIAGE OF THE OLD CODE DIDN'T VARY WITH THE NEW ONE
 THE REFERENCE IS INCORRECT.
 2. FROM THIS DRAWING IT IS VERY DIFFICULT TO RECOGNIZE
 WHAT AND WHERE WOULD THE DAYLIGHT ZONE BE FOR
 COMPLIANCE WITH THE FBC-EC402 & 405
 SHEET E2.1A
 1. NEC 225.34 RESTRICTS THE NUMBER OF DISCONNECTS AND
 REQUIRES THAT THEY BE GROUPED.
 SHEET E2.1B
 1. PANELS LA & LB DO NOT COMPLY WITH NEC 110.26
 SHEET E2.2A
 1. SEPARATE PERMIT AND SUBMITTAL REQUIRED FOR THE FIRE
 ALARM.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  