2016-04-13 18:52:32 | THIS PERMIT IS RIDING ALONG WITH16040415 AND ARE |
| SHARING THE PLANS, THEREFORE THE COMMENTS ARE COMMON TO |
| BOTH PERMIT. |
| |
| ELECTRICAL REVIEW COMMENTS |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| EDITION |
| |
| CORRECTIONS REQUIRED: |
| BLDG. DEPT. NOTES ON COVER SHEET |
| 1. A) INDICATE THAT THE PLANS WERE DESIGNED TO MEET THE |
| REQUIREMENTS OF THE 2008 NEC. D) REFERS TO THE LATEST |
| CODE. THE 2011 EDITION OF THE NEC IS THE ONE CURRENTLY |
| ADOPTED BUT IT IS NOT THE LATEST EDITION. |
| SHEET E2.0A |
| 1. NOTE 14 AGAIN REFERS TO AN OLD CODE. THOUGH THE |
| VERBIAGE OF THE OLD CODE DIDN'T VARY WITH THE NEW ONE |
| THE REFERENCE IS INCORRECT. |
| 2. FROM THIS DRAWING IT IS VERY DIFFICULT TO RECOGNIZE |
| WHAT AND WHERE WOULD THE DAYLIGHT ZONE BE FOR |
| COMPLIANCE WITH THE FBC-EC402 & 405 |
| SHEET E2.1A |
| 1. NEC 225.34 RESTRICTS THE NUMBER OF DISCONNECTS AND |
| REQUIRES THAT THEY BE GROUPED. |
| SHEET E2.1B |
| 1. PANELS LA & LB DO NOT COMPLY WITH NEC 110.26 |
| SHEET E2.2A |
| 1. SEPARATE PERMIT AND SUBMITTAL REQUIRED FOR THE FIRE |
| ALARM. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |