Plan Review Notes
Plan Review Notes For Permit 16040412
Permit Number 16040412
Review Stop B
Sequence Number 1
Notes
Date Text
2016-05-04 15:08:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040412
 ADD: 1600 N DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: (561)662-1927
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 04/2016
 ACTION: DENIED
  
 1A) THE COVER SHEET INDICATES THE PLANS WERE DEVELOPED
 TO THE 2010 FBC CODE. STATEWIDE JUNE 30/2015 THE 2014
 FBC-B/ 5TH EDITION WAS ADOPTED STATEWIDE.
  
 1B) THE COVERSHEET THE INDEX IS MISSING (4) SHEETS THAT
 ARE IN THE PLAN SET. SHEET D-2.0, A-1.0, A-2.1 & A-7.1.
  
 1C) THE COVERSHEET INDIATES THIS FACILITY CURRENTLY
 DOES NOT HAVE FIRE SPRINKLERS, THIS IS A CHANGE OF
 OCCUPANCY FROM A LOUNGE A2 TO A B OCCUPANCY/ AMBULATORY
 CARE FACILITY.
 2014 EXIST. BLDG. CODE SECTION 1004 FIRE PROTECTION.
 1004.1. FIRE PROTECTION REQUIREMENTS OF SECTION 1012
 SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF
 UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION.
  
 2014 EXISTING BLDG CODE. 1012.1.1 COMPLIANCE WITH
 CHAPTER 9. THE REQUIREMENTS OF CHAPTER 9 SHALL BE
 APPLICABLE THROUGHOUT THE BUILDING FOR THE NEW
 OCCUPANCY CLASSIFICATION BASED ON THE SEPARATION
 CONDITIONS SET FORTH IN SECTIONS 1012.1.1.1 AND
 1012.1.1.2.
  
 2014 EXISTING BLDG CODE. 1012.2.1 FIRE SPRINKLER
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS.
  
 2014 FBC-B [F] 903.2.2 AMBULATORY CARE FACILITIES. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED
 THROUGHOUT THE ENTIRE FLOOR CONTAINING AN AMBULATORY
 CARE FACILITY WHERE EITHER OF THE FOLLOWING CONDITIONS
 EXIST AT ANY TIME:
  
 1. FOUR OR MORE CARE RECIPIENTS ARE INCAPABLE OF SELF
 PRESERVATION, WHETHER RENDERED INCAPABLE BY STAFF OR
 STAFF HAS ACCEPTED RESPONSIBILITY FOR CARE RECIPIENTS
 ALREADY INCAPABLE.
  
 2. ONE OR MORE CARE RECIPIENTS THAT ARE INCAPABLE OF
 SELF-PRESERVATION ARE LOCATED AT OTHER THAN THE LEVEL
 OF EXIT DISCHARGE SERVING SUCH A FACILITY.
  
 2) SHEET A-1.0 INDICATES THE PROPOSED SITE PLAN. THIS
 IS AN UNUSUAL BUILDING SINCE NONE OF THE TENANT SPACE
 (1600 N DIXIE) HAVE DOORWAYS THAT EXIT ONTO A PUBLIC
 RIGHT OF WAY. PLEASE PROVIDE A SITE PLAN SHOWING
 COMPLIANCE WITH:
 2A) 2014 FBC-B 1027.5 ACCESS TO A PUBLIC WAY. THE EXIT
 DISCHARGE SHALL PROVIDE A DIRECT AND UNOBSTRUCTED
 ACCESS TO A PUBLIC WAY.
 2B) 2014 FBC-ACCESSIBILITY CODE 206.2.4 SPACES AND
 ELEMENTS. AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDING OR FACILITY ENTRANCES WITH ALL
 ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION
 PATH TO THE PUBLIC WAY, UNLESS EXEMPTED BY 206.2.3
 EXCEPTIONS 1 THROUGH 7.
 2C) 2014 FBC-ACCESSIBILITY 208.3.1 WHERE IN THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE THE PATRON IS
 NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED CARS.
 3) SHEET LS-1.0A SHOWS (2) 1 HOUR FIRE SEPARATION WALLS
 LOCATED AT THE PROPERTY LINE. THERE ARE 2 LLC
 CORPORATIONS THAT OWN THE BUILDING AT 1600 N. DIXIE AND
 1522 N. DIXIE. NO UNITY OF TITLE CAN OCCUR FOR THIS
 SITE WITH DIFFERENT OWNERS. THE ISSUE WITH THE DOORWAY
 BEING CUT INTO THE PROPERTY LINE WALL THESE ARE
 CONSIDERED AS BOTH BEING 1 HOUR FIRE RATED WALLS. SINCE
 THERE IS ONLY ONE COMMON WALL SEPARATING THE 2
 PROPERTIES, THIS PORTION OF WALL WILL NEED TO BE
 CONSIDERED A PARTY WALL SEE 2014 FBC-B 706.1.1 & TABLE
 706.4. ( 3 HOURS) & TABLE 716.5 OPENINGS IN FIRE WALLS
 ( 3 HOURS).
 4) SHEET LS-1.0A DOES THE DOORS 30, 31 & ER HAVE AN
 ACCESSIBLE ENTRY/ EXIT , LEVEL WITH GRADE? 2014
 FBC-ACCESS. CODE 206.2.4 SPACES AND ELEMENTS. AT LEAST
 ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDING
 OR FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY WHICH ARE
 OTHERWISE CONNECTED BY A CIRCULATION PATH UNLESS
 EXEMPTED BY 206.2.3 EXCEPTIONS 1 THROUGH 7.
 5) SHEET LS-1A THE OCCUPANT LOADS OF BUSINESS 23.24,
 STORAGE 1.03 & CONFERENCE ROOM 52.86 OCCUPANTS. IN EACH
 CASE THE OCCUPANT LOAD IS ROUNDED DOWN. PLEASE NOTE YOU
 ALWAYS ROUND UP TO THE NEXT WHOLE NUMBER. FLORIDA
 BUILDING CODE INFORMAL INTERPRETATION REPORT # 5479.
 DATE: TUE DEC 18 2007
 REPORT #: 5479
 CODE: BUILDING
 SECTION: 1004.1.2
 QUESTION:
 IS IT THE INTENT OF SECTION 1004.1.2 TO ALLOW THE
 LARGEST NUMBER COMPUTED IN ACCORDANCE WITH
 TABLE 1004.1.2 TO BE ROUNDED TO THE NEAREST WHOLE
 NUMBER? COMMENT: FOR EXAMPLE, A
 BUSINESS OCCUPANCY IN A BUILDING WITH 3215 GROSS SQUARE
 FEET, CALCULATED OCCUPANCY LOAD
 WOULD BE 32.15 WOULD I ROUND DOWN TO 32 OCCUPANTS OR
 WOULD I BE REQUIRED TO ROUND UP TO
 33 OCCUPANTS
 ANSWER:
 ROUND UP TO 33
 COMMENTARY:
 OCCUPANTS ONLY COME AS A WHOLE.
  
 6) SHEET LS-1A SHOWS 1 HOUR RATED WALLS IN THE STORAGE
 ROOMS WITH THE WALL TYPE IDENTIFIED AS WALL TYPE F, A
 UL U-465 FIRE RATED WALL. PLEASE PROVIDE THE UL DETAIL
 FOR THE INSPECTOR WILL BE ABLE TO IDENTIFY THE VARIOUS
 COMPONENTS OF THE WALL ASSEMBLY. 2014 FBC-B 707.3 FIRE
 ?RESISTANCE RATINGS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 7) DOOR 31 & 32 ARE NEW EXTERIOR DOORS, WILL NEED TO
 COMPLY WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) PLEASE PROVIDE THE PRESSURES BOTH POSITIVE AND
 NEGATIVE FOR THESE DOORS IN VASD. 2014 FBC-B 1603.1.4
 WIND DESIGN DATA.
  
 10) THE MECHANICAL SHEET M-3.1 SHOWS THE ROOF TOP UNITS
 BEING ATTACHED TO THE ROOF TOP CURBS. PLEASE NOTE THAT
 RTU CURBS WERE REVIEWED AND INSPECTED UNDER PERMIT #
 15100589. PLEASE NOTE THE WIND DESIGN FOR THE ANCHORING
 OF THE RTU UNIT TO CURB IS 150 MPH. PLEASE CORRECT THE
 WIND DESIGN AND CALCULATIONS FOR ANCHORING OF THE RTU
 TO CURB. THIS IS A 170 VULT MPH WIND ZONE FOR BUILDINGS
 WITH AN BUILDING RISK CATEGORY II. SEE 2014 FBC-B
 FIGURE 1609A.
  
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  