Plan Review Notes For Permit 16040411 |
Permit Number |
16040411 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-19 13:49:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE THE FLOOR PLAN TO PROVIDE THE FOLLOWING | | INFORMATION: WINDOW TYPE IN EACH OPENING, ROOM | | DESIGNATIONS. FBC 107, PLAN SHOULD BE CLEAR AS TO | | SCOPE. TWO DIFFERENT WINDOW PRODUCT APPROVALS PROVIDED, | | ONE IMPACT AND ONE NON IMPACT, AND A MULLION PRODUCT | | APPROVAL. FLOOR PLAN APPEARS TO SHOW A WINDOW AND A | | DOOR. REVISE FLOOR PLAN TO SHOW PROPOSED INSTALLATION, | | SIZES OF INDIVIDUAL WINDOWS, MULLION SPAN. SCOPE IS NOT | | ADEQUATELY SHOWN. | | | | 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND | | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 704.1. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | | | |
|