Plan Review Notes For Permit 16040372 |
Permit Number |
16040372 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-07-23 03:31:04 | 1)THE PLAN REVIEW COMMENTS FROM THE REVIEW DONE ON | | 5/9/16 AND ALSO ON 7/12/16 HAVE NOT BEEN ADEQUATELY | | ADDRESSED.COMPLY WITH ALL PREVIOUS REVIEW COMMENTS. | | 2) THE DRINKING FOUNTAINS SHALL COMPLY WITH THE 2014 | | FL. ACCESSIBILITY CODE SEC.211.2 AND SECS.602.1THROUGH | | 602.6 AND 602.7 AND FIGURE 602.5. SUBMIT MANUFACTURER'S | | SPECIFICATION SHEETS FOR THE UNIT. THE DETAIL ON SHT. | | T3.2 DOES NOT SHOW COMPLIANCE WITH THE CITED CODE | | SECTIONS. BOTH UNITS APPEAR TO BE AT THE SAME | | ELEVATION. | | 3) THIS IS THE THIRD REJECTION FOR THE SAME COMMENTS | | AND YOU WILL BE CHARGED FOUR TIMES THE PLAN REVIEW FEE | | ON THE NEXT SUBMITTAL IN ACCORDANCE WITH FL. STATUTE | | 553.80. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|