Plan Review Notes
Plan Review Notes For Permit 16040372
Permit Number 16040372
Review Stop P
Sequence Number 3
Notes
Date Text
2016-07-23 03:31:041)THE PLAN REVIEW COMMENTS FROM THE REVIEW DONE ON
 5/9/16 AND ALSO ON 7/12/16 HAVE NOT BEEN ADEQUATELY
 ADDRESSED.COMPLY WITH ALL PREVIOUS REVIEW COMMENTS.
 2) THE DRINKING FOUNTAINS SHALL COMPLY WITH THE 2014
 FL. ACCESSIBILITY CODE SEC.211.2 AND SECS.602.1THROUGH
 602.6 AND 602.7 AND FIGURE 602.5. SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE UNIT. THE DETAIL ON SHT.
 T3.2 DOES NOT SHOW COMPLIANCE WITH THE CITED CODE
 SECTIONS. BOTH UNITS APPEAR TO BE AT THE SAME
 ELEVATION.
 3) THIS IS THE THIRD REJECTION FOR THE SAME COMMENTS
 AND YOU WILL BE CHARGED FOUR TIMES THE PLAN REVIEW FEE
 ON THE NEXT SUBMITTAL IN ACCORDANCE WITH FL. STATUTE
 553.80.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  