2016-08-10 14:34:493RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16040364
 8/10/16
  
 1) SHEET S-01: THE CHILLER ATTACHMENT DETAIL INDICATES
 THE CLEARANCE DISTANCE BETWEEN THE ROOF SURFACE AND THE
 NEW CHILLER IS INSUFFICIENT PER TABLE 1509.6.5 FBC-14
 BUILDING. IF THE CONTRACTOR AND DESIGN PROFESSIONAL'S
 INTENTION IS TO SOMEHOW PROVE THAT THE CURRENT DESIGN
 IS ADEQUATE OR EQUAL TO WHAT IS REQUIRED BY CODE, THEN
 AN ALTERNATE DESIGN PROPOSAL WOULD HAVE TO BE SUBMITTED
 TO THE BUILDING OFFICIAL. PLEASE REVIEW SECTION 104.11
 WPB AMENDMENTS TO THE FBC:
  
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION A N D E Q U I P M E N T. T H E PROVISIONS
 O F T H IS C O D E A RE N O T INTENDED TO PREVENT THE
 INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED B
 Y T H I S C O D E , P R O V I D E D T H A T A N Y S U C
 H A L T E R N A T I V E H A S BEEN APPROVED. AN
 ALTERNATIVE MATERIAL, DESIGN OR METHOD OF CONSTRUCTION
 SHALL BE APPROVED WHERE THE BUILDING OFFICIAL FINDS
 THAT THE PROPOSED DESIGN IS SATISFACTORY AND COMPLIES
 WITH THE INTENT OF THE
 PROVISIONS OF THIS CODE, AND THAT THE MATERIAL, METHOD
 OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT LEAST
 THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE LIFE SAFETY
 SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND DESIGN
 OF BUILDINGS, OR OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING OFFICIAL SHALL
 REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE SUBMITTED
 TO SUBSTANTIATE
 ANY CLAIM MADE REGARDING THE ALTERNATIVE.
  
 2) COMMENT #1B FROM THE 1ST REVIEW HAS NOT BEEN FULLY
 ADDRESSED. THE CHILLER DETAIL DOES NOT INDICATE HOW THE
 CHILLER WILL BE ANCHORED OR FASTENED TO THE NEW STEEL
 BEAM TO RESIST WIND PRESSURES- SECTION 301.15, AND DOES
 NOT PROVIDE THE DIMENSIONS OF THE CHILLER.
  