2016-08-10 14:34:49 | 3RD REVIEW FBC-2014 MECHANICAL |
| PERMIT #16040364 |
| 8/10/16 |
| |
| 1) SHEET S-01: THE CHILLER ATTACHMENT DETAIL INDICATES |
| THE CLEARANCE DISTANCE BETWEEN THE ROOF SURFACE AND THE |
| NEW CHILLER IS INSUFFICIENT PER TABLE 1509.6.5 FBC-14 |
| BUILDING. IF THE CONTRACTOR AND DESIGN PROFESSIONAL'S |
| INTENTION IS TO SOMEHOW PROVE THAT THE CURRENT DESIGN |
| IS ADEQUATE OR EQUAL TO WHAT IS REQUIRED BY CODE, THEN |
| AN ALTERNATE DESIGN PROPOSAL WOULD HAVE TO BE SUBMITTED |
| TO THE BUILDING OFFICIAL. PLEASE REVIEW SECTION 104.11 |
| WPB AMENDMENTS TO THE FBC: |
| |
| 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF |
| CONSTRUCTION A N D E Q U I P M E N T. T H E PROVISIONS |
| O F T H IS C O D E A RE N O T INTENDED TO PREVENT THE |
| INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN |
| OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED B |
| Y T H I S C O D E , P R O V I D E D T H A T A N Y S U C |
| H A L T E R N A T I V E H A S BEEN APPROVED. AN |
| ALTERNATIVE MATERIAL, DESIGN OR METHOD OF CONSTRUCTION |
| SHALL BE APPROVED WHERE THE BUILDING OFFICIAL FINDS |
| THAT THE PROPOSED DESIGN IS SATISFACTORY AND COMPLIES |
| WITH THE INTENT OF THE |
| PROVISIONS OF THIS CODE, AND THAT THE MATERIAL, METHOD |
| OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT LEAST |
| THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN |
| QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| DURABILITY AND SAFETY. WHEN ALTERNATE LIFE SAFETY |
| SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE TO |
| PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND DESIGN |
| OF BUILDINGS, OR OTHER METHODS APPROVED BY THE BUILDING |
| OFFICIAL MAY BE USED. THE BUILDING OFFICIAL SHALL |
| REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE SUBMITTED |
| TO SUBSTANTIATE |
| ANY CLAIM MADE REGARDING THE ALTERNATIVE. |
| |
| 2) COMMENT #1B FROM THE 1ST REVIEW HAS NOT BEEN FULLY |
| ADDRESSED. THE CHILLER DETAIL DOES NOT INDICATE HOW THE |
| CHILLER WILL BE ANCHORED OR FASTENED TO THE NEW STEEL |
| BEAM TO RESIST WIND PRESSURES- SECTION 301.15, AND DOES |
| NOT PROVIDE THE DIMENSIONS OF THE CHILLER. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |