Plan Review Notes
Plan Review Notes For Permit 16040364
Permit Number 16040364
Review Stop M
Sequence Number 2
Notes
Date Text
2016-04-29 17:00:372ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040364
 4/29/16
  
 1) M-1.1: THE REQUESTED WIND LOAD ENGINEERING FOR THE
 ROOFTOP CHILLER INSTALLATION IS INCOMPLETE: A) PROVIDE
 THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE WITH
 SECTION 1609 FBC-14 BUILDING. B) PROVIDE DIMENSIONED
 PLAN AND SECTION VIEWS OF THE CHILLER AND SUPPORT BASE
 THAT INDICATE THE TYPE AND SIZE OF FASTENERS AND
 ANCHORS FOR ATTACHING THE I-BEAMS TO THE PIERS, THE
 RAILS TO THE I-BEAMS AND THE CHILLER TO THE RAILS. C)
 INDICATE THE CLEARANCE HEIGHT FROM THE ROOF SURFACE TO
 THE UNDERSIDE OF THE CHILLER SUPPORT STRUCTURE- SECTION
 2) M-1.1: NOTE #1 REFERENCES SHEET M-6.2 WHICH IS NOT
 INCLUDED IN THE PLAN SETS. NOTE #4 REFERENCES SHEET
 M-5.2 WHICH IS NOT IN THE PLAN SETS.
 3) M-1.1: INDICATE THE SIZES OF THE NEW CHILLED WATER
 PIPING.
 4) M-5.1: THE CHILLER SCHEDULE INDICATES A 9.0
 EFFICIENCY RATE FOR THE UNIT, HOWEVER A MINIMUM FULL
 LOAD EFFICIENCY RATING OF 9.562 IS REQUIRED PER TABLE
 C403.2.3(7) FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  