Plan Review Notes For Permit 16040364 |
Permit Number |
16040364 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-04-29 17:00:37 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #16040364 | | 4/29/16 | | | | 1) M-1.1: THE REQUESTED WIND LOAD ENGINEERING FOR THE | | ROOFTOP CHILLER INSTALLATION IS INCOMPLETE: A) PROVIDE | | THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE WITH | | SECTION 1609 FBC-14 BUILDING. B) PROVIDE DIMENSIONED | | PLAN AND SECTION VIEWS OF THE CHILLER AND SUPPORT BASE | | THAT INDICATE THE TYPE AND SIZE OF FASTENERS AND | | ANCHORS FOR ATTACHING THE I-BEAMS TO THE PIERS, THE | | RAILS TO THE I-BEAMS AND THE CHILLER TO THE RAILS. C) | | INDICATE THE CLEARANCE HEIGHT FROM THE ROOF SURFACE TO | | THE UNDERSIDE OF THE CHILLER SUPPORT STRUCTURE- SECTION | | 2) M-1.1: NOTE #1 REFERENCES SHEET M-6.2 WHICH IS NOT | | INCLUDED IN THE PLAN SETS. NOTE #4 REFERENCES SHEET | | M-5.2 WHICH IS NOT IN THE PLAN SETS. | | 3) M-1.1: INDICATE THE SIZES OF THE NEW CHILLED WATER | | PIPING. | | 4) M-5.1: THE CHILLER SCHEDULE INDICATES A 9.0 | | EFFICIENCY RATE FOR THE UNIT, HOWEVER A MINIMUM FULL | | LOAD EFFICIENCY RATING OF 9.562 IS REQUIRED PER TABLE | | C403.2.3(7) FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|