2016-04-20 08:26:37 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16040364 |
| ADD: 2201 45TH ST. / REPLACE CHILLERS & INSTALL SCREEN |
| WALL |
| CONT: AIRSTRON INC. |
| TEL: 954-923-1654 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. APRIL 20/2016 |
| ACTION: DENIED |
| |
| 1) SHEET S1 SCREEN WALL DOES NOT INDICATE THE TYPE OF |
| FASTENERS TO BE USED IN ANCHORING OF THE NEW SCREEN |
| WALL. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 2) THE SHEET S1 INDICATES THE SCREEN WALL SCREEN IS TO |
| HAVE PRODUCT APPROVALS, SPECIFIC A MIAMI-DADE (NOA). |
| NOT SUBMITTED IN THIS PERMIT PACKET. TYPE OF |
| CONSTRUCTION MINIMUM BUILDING TYPE FBC-B TABLE 503. |
| ALSO UNKNOWN FIRE SEPARATION DISTANCE. |
| 2014 FBC-B ? 1509.6 MECHANICAL EQUIPMENT SCREENS. |
| MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF |
| THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN |
| ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE |
| BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER |
| THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS |
| SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| FIRE-RESISTANCE RATING REQUIREMENTS. |
| |
| 3) 2014 FBC-B ? 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL |
| EQUIPMENT SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN |
| HEIGHT ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST |
| POINT ON THE MECHANICAL EQUIPMENT SCREEN. EXCEPTION: |
| WHERE LOCATED ON BUILDINGS OF TYPE IA CONSTRUCTION, THE |
| HEIGHT OF MECHANICAL EQUIPMENT SCREENS SHALL NOT BE |
| LIMITED. |
| |
| 4) THE STRUCTURAL SHEET NOR MEHANICAL SHEETS SHOW HOW |
| THE NEWCHILLER IS GOING TO BE ANCHORED TO THE CURB TO |
| RESIST SLIDDING AND OVERTURNING. |
| 2014 FBC-B LATERAL FORCE-RESISTING SYSTEM |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |