2016-04-20 08:26:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040364
 ADD: 2201 45TH ST. / REPLACE CHILLERS & INSTALL SCREEN
 WALL
 CONT: AIRSTRON INC.
 TEL: 954-923-1654
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 20/2016
 ACTION: DENIED
  
 1) SHEET S1 SCREEN WALL DOES NOT INDICATE THE TYPE OF
 FASTENERS TO BE USED IN ANCHORING OF THE NEW SCREEN
 WALL.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 2) THE SHEET S1 INDICATES THE SCREEN WALL SCREEN IS TO
 HAVE PRODUCT APPROVALS, SPECIFIC A MIAMI-DADE (NOA).
 NOT SUBMITTED IN THIS PERMIT PACKET. TYPE OF
 CONSTRUCTION MINIMUM BUILDING TYPE FBC-B TABLE 503.
 ALSO UNKNOWN FIRE SEPARATION DISTANCE.
 2014 FBC-B ? 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 3) 2014 FBC-B ? 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL
 EQUIPMENT SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN
 HEIGHT ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST
 POINT ON THE MECHANICAL EQUIPMENT SCREEN. EXCEPTION:
 WHERE LOCATED ON BUILDINGS OF TYPE IA CONSTRUCTION, THE
 HEIGHT OF MECHANICAL EQUIPMENT SCREENS SHALL NOT BE
 LIMITED.
  
 4) THE STRUCTURAL SHEET NOR MEHANICAL SHEETS SHOW HOW
 THE NEWCHILLER IS GOING TO BE ANCHORED TO THE CURB TO
 RESIST SLIDDING AND OVERTURNING.
 2014 FBC-B LATERAL FORCE-RESISTING SYSTEM
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  