Plan Review Notes
Plan Review Notes For Permit 16040300
Permit Number 16040300
Review Stop B
Sequence Number 2
Notes
Date Text
2016-06-29 19:01:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLORIDA LICENSED ENGINEER IS REQUIRED TO SIGN BY
 HAND HIS HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) ON THE PLANS AND OTHER CONSTRUCTION
 DOCUMENTS. FAC 61G15-23.002 DIGITAL SIGNATURES ARE ONLY
 ACCEPTABLE ON ELECTRONICALLY SUBMITTED DOCUMENTS.
 FAC61G15-23.003
  
 2) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING
 DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY
 SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY
 INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR
 WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1 SUBMIT
 A SIGNED AND SEALED LETTER FROM THE ENGINEER CERTIFYING
 THAT HE HAS REVIEWED THE STRUCTURE AND FOUND IT TO BE
 STRUCTURALLY CAPABLE OF SAFELY SUPPORTING ALL
 ADDITIONAL LOADING THAT WILL BE CREATED BY INSTALLATION
 OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR WATER HEATER
 COLLECTOR ON THE ROOF.
  
  