2016-04-07 10:24:16 | JOB PERMIT NUMBER: 16040300 |
| JOB ADDRESS: 201 SANTA LUCIA DR |
| WEST PALM BEACH FLORIDA |
| DATE: APRIL 7, 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - THE SCOPE OF WORK ACCORDING TO FLORIDA STATUE |
| 61G4-15.021 LIMITS THE CVC CONTRACTOR TO THE PV SUPPLY |
| SIDE , THEREFORE ANY CONNECTION TO THE ELECTRICAL |
| BUILDING PREMISES MUST BE DONE BY A LICENSED ELECTRICAL |
| CONTRACTOR. |
| - PLANS ARE MISSING LABELS AND MARKINGS |
| 1 NEC 690.5 C GROUND FAULT PROTECTION |
| 2 NEC 690.14 C 2 PERMANENTLY MARK DISCONNECT |
| 3 NEC 690.31 E 3 IDENTIFY PV SOURCE CONDUCTORS |
| 4 NEC 705.12 7 DO NOT RELOCATE SOURCE DISCONNECT |
| - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014 |
| |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |