2016-04-08 11:06:59 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THERE ARE NOT ANY REFERENCES OR DRAWINGS ON THE |
| APPROVED PLANS THAT SHOW THE PHOTOVOLTAIC OR SOLAR |
| WATER HEATER COLLECTOR ON THE ROOF OF THE MANUFACTURED |
| BUILDING. THIS A SEPARATE PERMIT WITH AN APPLICATION |
| DATE THAT PLACES IT UNDER THE 2014 FLORIDA BUILDING |
| CODE RESIDENTIAL. THE APPLICABLE CODES ARE THE 2014 |
| FBC-R AND THE 2011 NEC. PLEASE REVISE THE PLANS |
| ACCORDINGLY. |
| |
| 2) THERE IS A SOLAR WATER HEATER COLLECTOR SHOWN ON |
| SHEET S-1 OF THE DRAWINGS, HOWEVER, NO OTHER |
| INFORMATION WAS PROVIDED. IF THIS IS TO BE INSTALLED, A |
| SEPARATE PERMIT, APPLICATION AND REVIEWS ARE REQUIRED. |
| |
| 3) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING |
| DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY |
| SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY |
| INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR |
| WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1 |
| |
| 4) THE STRUCTURAL MOUNTING DETAILS THAT WERE SUBMITTED |
| ON SHEET S-2 ARE FOR A DIFFERENT TYPE OF ROOF |
| CONSTRUCTION THAN THE ONE THAT WAS PERMITTED. THE |
| APPROVED PLANS SHOW A 60 MIL TPO MEMBRANE ROOF COVERING |
| OVER 1/4" TAPERED ISO OVER ZIP BOARD ROOF SHEATHING |
| ATTACHED TO 22 GA. STEEL 1-1/2" CORRUGATED B DECK ON 8" |
| X 2" 16 GA. STEEL JOISTS SPACED 24" O.C. THE |
| CALCULATIONS AND DETAILS THAT WERE SUBMITTED ARE FOR |
| ATTACHMENT TO WOOD TRUSSES USING LAG SCREWS. PLEASE |
| CORRECT. FBC 107.2.1 |