2016-04-08 10:05:531ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040257
 4/8/16
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL ALTERATIONS OR
 MODIFICATIONS TO THE EXISTING HVAC SYSTEMS.
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES AS REQUIRED BY SECTION 809.2
 FBC-14 EXISTING BUILDING CODE, AND TABLE 403.3 FBC-14
 MECHANICAL.
 3) THE PROPOSED PROJECT IS DEFINED AS A RENOVATION PER
 SECTION 202 FBC-14 ENERGY CONSERVATION. SEE SECTION
 C101.4.3 AND SUBMIT ENERGY CALCULATIONS USING EITHER
 THE PRESCRIPTIVE OR PERFROMANCE BASED COMPLIANCE PATH-
 SECTION C101.5.
  