| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014, |
| NEC 2008 NO LONGER APPLICABLE. |
| - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE |
| SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| FLOOR PLAN. THE PLANS ARE MISSING COFFEE MAKER , SHOWS |
| 2 DISHWASHER ON FLOOR PLANS AND CLACS REFLECT ONLY 1 , |
| REFLECT THESE LOADS ON PANEL A. |
| - ADD THE FOLLOWING GENERAL ELECTRICAL NOTES : NEC |
| 406.11 TAMPER RESISTANT RECEPTACLES , NEC 210.12 B AFCI |
| PROTECTION , FBC-E C 404.1.1 / 402.4.4 RECESSED LIGHTS |
| SHALL BE 75 % HIGH EFFICIENT AS WELL AS IC RATED AND |
| SEALED TO NOT COMPROMISE BUILDING THERMAL ENVELOPE. ( 2 |
| CFM ) |
| - NEC 404.2 C PROVIDE A GROUNDED CONDUCTOR AT EACH |
| SWITCH LOCATION. |
| - NEC 210.52 , 210.8 BALCONY RECEPTACLES MUST BE GFCI |
| PROTECTED. |
| - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE |
| DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910 |
| MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM |
| CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS. |
| RELOCATE THE UNITS ACCORDINGLY. ( BY GUEST BEDROOM 1 & |
| 2. ) |
| - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY |
| WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| SEALING MATERIAL. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |