Plan Review Notes For Permit 16040252 |
Permit Number |
16040252 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-28 12:01:42 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16040252 | | 4/6/16 | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW SYSTEM- SECTION C403.2.1 FBC-14 ENERGY | | CONSERVATION. | | 2) CLARIFY THE LOCATION OF THE NEW AHU-1. NOTE 1 ON | | SHEET M0.1 IS INDICATING THE CU LOCATION. | | 3) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR | | INSTALLATION OF THE CU ON THE ROOF RACK. SUBMIT AN NOA | | OR FL. PRODUCT APPROVAL FOR THE RACK WITH APPROVAL | | SIGNATURE BY THE EOR- SECTION 301.15 FBC-14 MECHANICAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | | | | | | | | 2016-04-06 07:03:28 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16040252 | | 4/6/16 | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW SYSTEM- SECTION C403.2.1 FBC-14 ENERGY | | CONSERVATION. | | 2) CLARIFY THE LOCATION OF THE NEW AHU-1. NOTE 1 ON | | SHEET M0.1 IS INDICATING THE CU LOCATION. | | 3) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR | | INSTALLATION OF THE CU ON THE ROOF RACK. SUBMIT AN NOA | | OR FL. PRODUCT APPROVAL FOR THE RACK WITH APPROVAL | | SIGNATURE BY THE EOR- SECTION 301.15 FBC-14 MECHANICAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|