Plan Review Notes
Plan Review Notes For Permit 16040227
Permit Number 16040227
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-07 04:54:411) IS THIS AN EXACT REPLACEMENT OF AN EXISTING BOILER
 OR IS THIS BEING ADDED? THE APPLICATION STATES "SUPPLY
 AND INSTALL "NEW" GAS BOILER. CLARIFY. IF IT IS AN
 EXACT REPLACEMENT, NOTE SUCH ON THE APPLICATION.
 2) WILL THE BOILER BE CONNECTED TO AN EXISTING VENT OR
 WILL A NEW VENT BE INSTALLED? IF A NEW VENT IS TO BE
 INSTALLED, SUBMIT A DETAIL SHOWING THE TYPE, LOCATION,
 SIZE AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL
 GAS SECS. 502 THRU 505.
 3) WILL ANY GAS PIPING OR WATER/BOILER PIPING HAVE TO
 BE ALTERED OR CHANGED? IF SO, SUBMIT A PIPING RISER FOR
 THE CHANGES THAT WILL BE MADE TO THE GAS AND WATER
 SYSTEMS.
 4) SUBMIT TWO COPIES OF DOCUMENTATION THAT THE BOILER
 IS LISTED IN ACCORDANCE WITH THE STANDARDS ANSI Z21.13
 OR UL 795 PER THE 2014 FGC SEC.631.1 AND IF APPLICABLE,
 THE ADDITIONAL STANDARDS LISTED IN THE FGC SEC. 631.1.
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. 2014 FBC 107.1, 2014 FGC SEC.631.2.
 6) CLEARANCE TO CCOMBUSTIBLE MATERIALS SHALL COMPLY
 WITH FGC SEC.631.3 & 308.4 OF 2015 FGC.
 7) CLEARANCES FROM THE TOPS OF BOILERS TO THE CEILING
 OR OTHER OVERHEAD OBSTRUCTION SHALL BE IN ACCORDANCE
 WITH 2014 FBC-MECHANICAL SEC.1004.3.1 & TABLE 1004.3.1.
 8) SUBMIT A FLOOR PLAN THAT REFLECTS THE ABOVE
 CONDITIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  