Plan Review Notes
Plan Review Notes For Permit 16040196
Permit Number 16040196
Review Stop G
Sequence Number 1
Notes
Date Text
2016-05-12 09:05:111ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 (1) THE PRESURE ON THE OUTLET OF THE METER IS UNCLEAR
 IF IT IS .5 LBS. YOU DON'T NEED A LOW PRESURE
 REGULATOR. PLEASE CLARIFY. PER WPBAMEND.TO FBC 107.2.1
  
 (2) IF IT IS REQUIRED TO HAVE A METER YOU NEED A VALVE
 UPSTEAM OF METER AND A SEDIMIT TRAP UP STEAM OF THE
 REGULATOR AND SHALL COMPLY WITH.
  
 2014 FBC GAS SEC.
  
 410.2 MP REGULATORS. MP PRESSURE REGULATORS SHALL
 COMPLY WITH THE FOLLOWING:
  
 1. THE MP REGULATOR SHALL BE APPROVED AND SHALL BE
 SUITABLE FOR THE INLET AND OUTLET GAS PRESSURES FOR THE
 APPLICATION.
  
 2. THE MP REGULATOR SHALL MAINTAIN A REDUCED OUTLET
 PRESSURE UNDER LOCKUP (NO-FLOW) CONDITIONS.
  
 3. THE CAPACITY OF THE MP REGULATOR, DETERMINED BY
 PUBLISHED RATINGS OF ITS MANUFACTURER, SHALL BE
 ADEQUATE TO SUPPLY THE APPLIANCES SERVED.
  
 4. THE MP PRESSURE REGULATOR SHALL BE PROVIDED WITH
 ACCESS. WHERE LOCATED INDOORS, THE REGULATOR SHALL BE
 VENTED TO THE OUTDOORS OR SHALL BE EQUIPPED WITH A
 LEAK-LIMITING DEVICE, IN EITHER CASE COMPLYING WITH
 SECTION 410.3.
  
 5. A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS
 UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL BE
 POSITIONED TO ALLOW CONNECTION OF A PRESSURE-MEASURING
 INSTRUMENT AND TO SERVE AS A SEDIMENT TRAP.
  
 6. A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED NOT LESS THAN 10 PIPE DIAMETERS
 DOWNSTREAM OF THE MP REGULATOR OUTLET. SUCH TEE FITTING
 SHALL BE POSITIONED TO ALLOW CONNECTION OF A
 PRESSURE-MEASURING INSTRUMENT.
  
 (3) A SEDIMET TRAP IS REQUIRED AT THE APPLIANCE.PER FBC
 GAS SEC. 408.4 SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE
 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT
 TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS,
 DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED
 FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT
 BE SO EQUIPPED.