2016-04-21 10:14:04 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16040196 |
| ADD: 531 SOUTHERN BLVD SUITE # ???? |
| CONT: ALONSO & ASSOCIATES |
| TEL: 561-837-9820 |
| E-MAIL: AALONSO@ALONSOAND ASSOCIATES.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. APRIL 21/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET A-202: |
| |
| 1A) THE RESTROOM WILL NEED TO SHOW THE SIZE OF THE |
| LAVATORY TO SHOW COMPLIANCE WITH THE: |
| |
| 2014 FBC-ACCESSIBILITY CODE 604.3.1 SIZE. |
| CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| PERPENDICULAR FROM THE REAR WALL. |
| |
| 1B) THE RESTROOM ALSO SHOWS A SHOWER WITH A DEPTH OF 2 |
| FEET 8 INCHES, PLEASE PROVIDE COMPLIANCE WITH SECTION |
| 608.2.2 FBC-ACCESS. CODE MINIMUM DEPTH OF 36 INCHES. |
| |
| 1C) THE ACCESSIBLE RESTROOM SHOWER SHOWS A SEAT IN THE |
| SHOWER BUT THE WALL EXTENDS PAST THE END OF THE SEAT. |
| PLEASE REVIEW 2014 FBC-ACCESSIBILITY CODE FIGURE |
| 608.2.1 & FIGURE 608.2.2. |
| |
| 2) PLEASE SHOW AN ACCESSIBLE ENTRANCE INTO THE TENANT |
| SPACE. 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS |
| OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| BUILDING CODE (2003 EDITION). |
| |
| 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| |
| PLEASE NOTE IF THE NEW SWING DOOR IN THE NORTHEAST |
| CORNER OF THE BUILDING IS GOING TO BE THE ACCESSIBLE |
| ENTRANCE THEN THERE NEEDS TO BE A 5-0 FOOT TURNING |
| RADIUS AT THE DOOR. ACCESS. CODE |
| 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE |
| DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR |
| LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525 |
| MM) MINIMUM. |
| |
| 405.7.5 DOORWAYS. |
| WHERE DOORWAYS ARE LOCATED ADJACENT TO A RAMP LANDING, |
| MANEUVERING CLEARANCES REQUIRED BY 404.2.4 AND 404.3.2 |
| SHALL BE PERMITTED TO OVERLAP THE REQUIRED LANDING |
| AREA. SEE FIGURE 404.2.4.1(H) |
| THE TOP OF THE RAMP HAS TO TRANSITION INTO A LEVEL |
| LANDING AND HAVE 2-0 FEET BEFORE THE CLOSEST PORTION OF |
| THE DOOR. |
| |
| |
| 3) DISCREPANCY IN SHEETS A-202 & A-203. SHEET A-202 THE |
| TENANT SEPARATION WALL IS SHORTER THAN DEPICTED IN |
| A-203. DISCREPANCY, 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 4) SHEET A-201 IN THE NORTHEAST CORNER OF THE BUILDING |
| INDICATES THE REMOVAL OF A OVERHEAD DOOR. SHEET A-202 |
| SHOWS A NEW EXTERIOR SWING DOOR AND WALL INFILL. THE |
| PLANS DO NOT PROVIDE ANY INFORMATION AS TO WHAT |
| MATERIALS ARE TO BE USED IN THE INFILL, COLUMNS AND |
| BLOCK, STEEL STUDS, ETC? |
| 107.2.1.3 ADDITIONAL INFORMATION./ 107.3.5.1.1(8) |
| BUILDING ENVELOPE, MINIMUM PLAN REVIEW CRITERIA FOR |
| COMMERCIAL BUILDINGS. |
| |
| 5) THE PLANS WILL ALSO NEED TO PROVIDE COMPLIANCE WITH |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| 6A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS. |
| |
| 6B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC... |
| |
| 7) SHEET A-202 THE RESTROOM GRAB RAILS ARE MEASURED TO |
| THE CENTERLINE OF THE GRAB RAIL. PLEASE BE AWARE OF THE |
| CHANGE IN THE 2014 ACCESS. CODE FOR THE HEIGHT OF GRAB |
| BARS AND THE MEASURING OF GRAB BARS IS NOW FROM FINISH |
| FLOOR TO THE TOP OF THE GRASPING SURFACE OF THE GRAB |
| BAR. |
| 2014 FBC-ACCESS. CODE A609.4 POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |