2016-04-09 06:21:35 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. ELECTRICAL QUALIFIER TO SIGN DRAWINGS SUBMITTED PER |
| FBC 105.3.2.1 AS DESIGNER |
| 2. SHOW GENERAL NOTES TO INDICATE REQUIRED AFCI |
| PROTECTED CIRCUITS AND TAMPER RESISTANT RECEPTACLES PER |
| FBC RES E3902 AND E4002.14 |
| 3. PROVIDE A NOTE TO COMPLY WITH THE FBC EC |
| CODE-R404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS. |
| 4. SHOW ELECTRODE CONDUCTOR AT SERVICE TO REFLECT #6 |
| NOT #8 PER E3603.1 |
| 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| PER FBC RES E3609.3 |
| 6. LABEL KITCHEN AND BATHROOM RECEPTACLES GFCI |
| PROTECTED. |
| 7. CLARIFY IF THERE ARE EXISTING EXTERIOR FIXTURES FOR |
| EGRESS PER FBC RES E3903.3 |
| 8. SPACING REQUIREMENTS FOR RECEPTACLES TO BE ADDRESSED |
| IN THE LIVING ROOM AREA PER E3901.2.2 WALL SPACE |
| 9. PROVIDE A RECEPTACLE WITHIN 25FT FOR AC EQUIPMENT |
| EXTERIOR WP GFCI. PER FBC RES E3901.12 |
| 10. OUTDOOR RECEPTACLE REQUIRED PER FBC RES E3901.7, |
| FRONT AND BACK |
| 11. VERIFY THAT GDO OUTLET IS GFCI PROTECTED LABEL AS |
| SUCH ON PANEL SCHEDULE. E3902.2 |
| 12. SD/CO SMOKE DETECTORS REQUIRED ON THE EXTERIOR OF |
| BEDROOM DOORS FBC RES 315 |
| 13. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL |
| FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD |
| YOU HAVE ANY QUESTIONS OR CONCERNS. |
| |
| |
| |