2016-04-09 06:21:35INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ELECTRICAL QUALIFIER TO SIGN DRAWINGS SUBMITTED PER
 FBC 105.3.2.1 AS DESIGNER
 2. SHOW GENERAL NOTES TO INDICATE REQUIRED AFCI
 PROTECTED CIRCUITS AND TAMPER RESISTANT RECEPTACLES PER
 FBC RES E3902 AND E4002.14
 3. PROVIDE A NOTE TO COMPLY WITH THE FBC EC
 CODE-R404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS.
 4. SHOW ELECTRODE CONDUCTOR AT SERVICE TO REFLECT #6
 NOT #8 PER E3603.1
 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 6. LABEL KITCHEN AND BATHROOM RECEPTACLES GFCI
 PROTECTED.
 7. CLARIFY IF THERE ARE EXISTING EXTERIOR FIXTURES FOR
 EGRESS PER FBC RES E3903.3
 8. SPACING REQUIREMENTS FOR RECEPTACLES TO BE ADDRESSED
 IN THE LIVING ROOM AREA PER E3901.2.2 WALL SPACE
 9. PROVIDE A RECEPTACLE WITHIN 25FT FOR AC EQUIPMENT
 EXTERIOR WP GFCI. PER FBC RES E3901.12
 10. OUTDOOR RECEPTACLE REQUIRED PER FBC RES E3901.7,
 FRONT AND BACK
 11. VERIFY THAT GDO OUTLET IS GFCI PROTECTED LABEL AS
 SUCH ON PANEL SCHEDULE. E3902.2
 12. SD/CO SMOKE DETECTORS REQUIRED ON THE EXTERIOR OF
 BEDROOM DOORS FBC RES 315
 13. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  