2016-04-07 10:27:48WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 FLORIDA BUILDING CODE 5TH EDITION (2014)
 ENERGY CONSERVATION
  
 SECTION R202 RENOVATED BUILDINGS - A RESIDENTIAL OR
 NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS,
 OR EXTERIOR ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED
 COST OF RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED
 VALUE OF THE STRUCTURE.
  
 R403.6.1 - PROVIDE HEAT LOAD CALCULATIONS.
  
 107.2.1 - PROVIDE EQUIPMENT SCHEDULE FOR EXISTING HVAC
 EQUIPMENT.
  
 CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
 107.2.1 - PROVIDE CFM AMOUNTS AND SUPPLY GRILL
 DIMENSIONS FOR ALL SUPPLY AIR OUTLETS. PROVIDE
 EQUIPMENT SCHEDULE FOR REPLACEMENT BATH EXHAUST FANS.
  
 601.5 - PROVIDE RETURN AIR FOR ALL BEDROOMS. SHOW
 RETURN GRILL DIMENSIONS AND CFM QUANTITIES.