2016-04-07 10:25:25 | ELECTRICAL REVIEW COMMENTS |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| EDITION |
| |
| CORRECTIONS REQUIRED: |
| 1. PER FAC 61G4-15.021(D) THE SCOPE OF A CVC LICENSE |
| PROHIBITS THE CONNECTION OF THE PV SYSTEM INTO THE |
| INTEGRAL BLDG. WIRING. A LICENSED ELECTRICAL CONTRACTOR |
| IS REQUIRED TO SECURE A PERMIT FOR SAME. |
| 2. ACCORDING TO THE SUBMITTED PLANS, THE PROPOSED AC |
| INTERCONNECT CABLE IS TO BE A #10 AWG THWN-2 AND THE |
| SPEC SHEET PROVIDED FOR THE CABLE INDICATES IT TO BE A |
| #12 AWG THWN-2. |
| 3. PER NEC 705.12(7) INVERTER OUTPUT CONNECTION, A |
| PERMANENT LABEL SHALL BE APPLIED TO THE DISTRIBUTION |
| WITH THE FOLLOWING WORDING: WARNING INVERTER OUTPUT |
| CONNECTIONS DO NOT RELOCATE THIS OVERCURRENT DEVICE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |
2016-04-06 11:15:56 | I CALLED THE CONTRACTOR TO INQUIRE ON THE TYPE OF CABLE |
| BEING PROPOSED TO CONNECT THE INVERTERS TO THE JUNCTION |
| BOX. I ALSO HAD HIM CORRECTED THE STATION |
| IDENTIFICATION AND COST SAVINGS PARAMETERS TO A LOCAL |
| ADDRESS AS OPPOSED TO MIAMI FLORIDA. |