Plan Review Notes
Plan Review Notes For Permit 16040042
Permit Number 16040042
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-13 13:53:022ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS NOT ADDRESSED, PROVIDE A NARATIVE:
  
 1. PLEASE SHOW THE REQUIRED EM LIGHTING FOR THE SPACE
 UNDER SCOPE, EITHER BY WALL PACKS OR EM BALLAST. FBC
 107.3.5
 2. SHOW THE RECEPTACLES OUTLETS IN THE SPACE AND LABEL
 EXISTING IF NOT NEW. FBC 107.3.5
 3. LABEL CIRCUIT ID DESIGNATION FOR ALL LIGHTING AND
 RECEPTACLE OUTLETS TO CORRELATE WITH PANEL SCHEDULE
 SHOWN. FBC 107.3.5
 4. SHOW RTU ON ROOFTOP AND A RECEPTACLE OUTLET WITHIN
 25FT TO WP/WR GFCI PROTECTED. NEC 210.63
 5. CLARIFY IF THERE IS AN EXISTING SHOW WINDOW
 RECEPTACLES PER NEC 210.62
 7. PLANS TO BE SIGNED AND SEALED BY DESIGNER OF RECORD.
 FBC FLORIDA STATUE
 6. FEEL FREE TO CONTACT ME WITH ANY QUESTIONS OR
 CONCERNS.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  