Plan Review Notes
Plan Review Notes For Permit 16040042
Permit Number 16040042
Review Stop B
Sequence Number 2
Notes
Date Text
2016-08-12 10:33:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040042
 ADD: 1865 N. TAMARIND AVE.
 CONT: T. H. MOTTLEY
 TEL: 561-644-4081
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 12/2016
 ACTION: DENIED
  
 NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) PLEASE NOTE NO NARRATIVE SUBMITTED. ) WHEN
 RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1A) 2ND REQUEST. SHEET 2OF 6 THE CODE DATA INDICATES
 THE OCCUPANCY AS A A-2 OCCUPANCY BUT THE OCCUPANCY LOAD
 IS STATED AT 15. WITH THE OCCUPANT LOAD LESS THAN 50
 OCCUPANTS THIS OCCUPANCY IS CLASSIFIED AS A BUSINESS
 OCCUPANCY. THE PLANS SUBMITTED INDICATE THE KITCHEN 278
 SQ. FT./ 300= 1 NET. FBC-B TABLE 1004.1,2, COMMERCIAL
 KITCHENS ARE TO BE TAKEN AT 200 SQ. FT./ OCCUPANT. THE
 A-2 ASSEMBLY AREA IS 577 SQ. FT./ 15= 39 OCCUPANTS. 39
 +2= 41 OCCUPANTS.
  
 THIS REVIEW A SITE PLAN WAS SUBMITTED SHOW A DECK, 2
 PERGOLAS BUT AGAIN NO OUTSIDE SEASONAL SEATING THAT MAY
 MAKE THIS AN A2 OCCUPANCY.
 SEE 2014 FBC-B 303.1.1 SMALL BUILDINGS AND TENANT
 SPACES. A BUILDING OR TENANT SPACE USED FOR ASSEMBLY
 PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS
 SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.
  
 1B) NEW COMMENT THE PERMIT APPLICATION INDICATES UNDER
 THE DESCRIPTION OF WORK, PERGOLAS, WATER FOUNTAIN AND
 LANDSCAPING. UNDER THIS REVIEW SHEET 5OF 6 A SITE PLAN
 DOES INDICATE THESE ELEMENTS IN THE CONCEPT DRAWINGS.
 PLEASE NOTE NO ADDITIONAL PLANS HAVE BEEN SUBMITTED FOR
 ANY OF THESE ELEMENTS. EACH OF THESE ELEMENTS WILL
 REQUIRE A SEPARATE PERMIT AND PLANS. THIS FOR
 INSPECTION TRACKING PURPOSES AS WELL AS RECORD KEEPING.
 107.2.1.4 QUALITY OF BUILDING PLANS. . THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
  
  
  
 2)2ND REQUEST. SHEET 2 OF 6 INDICATES THIS BUILDING
 TYPE AS A BUILDING TYPE III-B. PLEASE PROVIDE A SURVEY
 FOR THE DISTANCE FROM THE PROPERTY LINES CAN BE
 ESTABLISHED AND CODE COMPLIANCE WITH:
 2014 FBC-B TABLE 602 & TABLE 705.8.
  
 3) 2ND REQUEST. PLEASE NOTE FIELD VERIFY THAT THE FRONT
 ENTRY IS AT GRADE. GOOGLE EARTH SHOWS SHUTTERS ACROSS
 THE FRONT DOOR, A SITE VISIT WILL BE REQUIRED. SHEET 4
 OF 6 SHOWS THE FRONT ENTRY AT GRADE. PLEASE VISIT THE
 SITE FOR VERIFICATION WITH THE FRONT ENTRY IS AN
 ACCESSIBLE ENTRY, THAT THE ENTRY IS FLUSH WITH THE
 EXTERIOR AND THERE IS A THRESHOLD OF NOT MORE THAN 1/2
 INCH IN HEIGHT.
 2014 FBC-ACCESS. CODE 404.3.3 THRESHOLDS. THRESHOLDS
 AND CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH
 404.2.5.
 2014 FBC-ACCESS. CODE 404.2.5 THRESHOLDS. THRESHOLDS,
 IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303. EXCEPTION:
 EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19 MM) HIGH
 MAXIMUM THAT HAVE A BEVELED EDGE ON EACH SIDE WITH A
 SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE REQUIRED TO
 COMPLY WITH 404.2.5.
  
 4) 2ND REQUEST. SHEET A-2 & A-4 BOTH INDICATES NEW
 WINDOWS AND DOORS, NO PRODUCT APPROVALS WERE SUBMITTED
 PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, IF INSTALLED, WALL
 LOUVERS,
 (D) IF INSTALLED, ROOFING PRODUCTS AND ASSEMBLIES,
 CURBS, INTAKE & EXHAUST ROOF TOP FANS, ROOF TOP RTUS
 (G) IF INSTALLED, PRE-ENGINEERED A/C STANDS
  
  
 5)2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6)2ND REQUEST. NOTICE COIL ROOF NAILS: ROOFING: NOTICE:
 EFFECTIVE APRIL 1/2016 THE REFERENCED MIAMI-DADE COUNTY
 ELECTROGALVANIZED FASTENERS LISTINGS ARE SUSPENDED:
 11--1019.02 & 11-1019.03 BLUELINX CORP.
 12-0423.06 CONTINENAL MATERIALS, INC.
 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC.
 13-0530.01 SPECIALTY FASTENING SYSTEM
 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC
 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO,
 LLC
  
 7) 2ND REQUEST. FOR ALL ROOF TOP EQUIPMENT, CURBS OR
 A/C STANDS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD
 EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS
 SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS
 THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY,
 GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 8A)2ND REQUEST DEPENDING ON THE PRODUCT APPROVALS FOR
 THE WINDOWS PRESSURES (MULLION) GIVEN MAYBE OR MAYBE
 NOT BE COMPLIANT FOR THE PRESSURES GIVEN ON 2 OF 6.
  
 8B) PLEASE NOTE SHEET 2 OF 6 LIST THIS IN A EXPOSURE D
 JOBSITE LOCATION. THE DESIGNER CAN DESIGN TO A MORE
 STRINGENT REQUIREMENT BUT THE PRESSURES WILL ALSO
 INCREASE AS WELL. THE PRESSURES GIVEN DO NOT STATE FOR
 WHAT SIZE OPENING THEY ARE FOR. SEE COMPONENTS &
 CLADDING PRESSURES POSITIVE & NEGATIVE FBC-B TABLE
 1609.2(2) .
  
 8C) NEW COMMENT. SHEET 2 OF 6 ON BOTH THE 1ST AND 2ND
 SET OF PLANS THE WIND DESIGN FOR BOTH THE ULTIMATE AND
 DESIGN WIND SPEED ARE BOTH 170 MPH, 3 SECOND GUST. 2014
 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 9) 2ND REQUEST. 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 10) 2ND REQUEST. 2014FBC-B 1509.6.4 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE
 EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT EXCEEDING
 16 FEET (4877 MM), SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
  
 11) 2ND REQUEST. PLEASE PROVIDE RESTROOM ELEVATIONS TO
 SHOW CODE COMPLIANCE FOR ACCESSIBLE RESTROOM ELEMENTS,
 PROVIDE WIDTH AND HEIGHT ELEVATION INCOMPLIANCE WITH
 2014 FBC-ACCESS. CHAPTER 6.
  
 12) 2ND REQUEST. SHOW COMPLIANCE WITH: 2014 FBC-ACCESS.
 CODE 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 13)2ND REQUEST. 2014 FBC-ACCESS. CODE 902.2 CLEAR FLOOR
 OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 14) 2ND REQUEST. 2014 FBC-ACCESS. CODE 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 15) 2ND REQUEST. 2014 FBC-ACCESS. CODE 703.1SIGNS SHALL
 COMPLY WITH 703. RESTROOM SIGNAGE. WHERE BOTH VISUAL
 AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN
 WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED
  
 16) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  