Plan Review Notes
Plan Review Notes For Permit 16040042
Permit Number 16040042
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-04-06 15:56:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET S 1 - PER NFPA 1 AND 101, THE INDICATED
 ASSEMBLY OCCUPANCY ISINCORRECT.
  
 PER NFPA 101, 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY.
 AN OCCUPANCY (1) USED FOR A GATHERING OF 50 OR MORE
 PERSONS FOR DELIBERATION, WORSHIP, ENTERTAINMENT,
 EATING, DRINKING, AMUSEMENT, AWAITING TRANSPORTATION,
 OR SIMILAR USES; OR (2) USED AS A SPECIAL
 AMUSEMENTBUILDING, REGARDLESS OF OCCUPANT LOAD.
  
 YOUR OCCUPANCY DOES NOT MEET THIS DEFINITION AND IS
 THEREFORE CLASSIFIED AS A MERCANTILE OCCUPANY. PER NFPA
 101 * "RESTAURANTS AND DRINKING ESTABLISHMENTS WITH AN
 OCCUPANT LOAD OF FEWER THAN 50 PERSONS SHOULD BE
 CLASSIFIED AS MERCANTILE
 OCCUPANCIES."
  
 THE OCCUPANCY SHALL COMPLY WITH NFPA 101, CHAPTER 36,
 NEW MERCANTILE OCCUPANCIES
  
 2. SHEET S 2 - AN EXISTING HOOD SYSTEM IS INDICATED.
 PER CHAPTER 36, 36.3.2.3 COOKING EQUIPMENT. COOKING
 EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 PLEASE INDICATE WITH A NOTE THAT THE SYSTEM IS
 CURRENTLY COMPLIANT WITH A SYSTEM CERTIFICATION TAG OR
 THE SYSTEM WILL HAVE A CURRENT CERTIFICATION TAG ON
 FINAL FIRE INSPECTION.
  
 3. SHEET S 2 - THE DOOR SCHEDULE DOES NOT INDICATE THE
 TYPE OF LOCKS OR HARDWARE. PER CHAPTER 36, 36.2.2.2
 DOORS.
  
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PER CHAPTER 7, MEANS OF EGRESS, 7.2.1.5.3 LOCKS, IF
 PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THESPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED
 AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN
 THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING
 OPERATION, UNLESS OTHERWISE SPECIFIED IN 7.2.1.5.10.3,
 7.2.1.5.10.4, OR 7.2.1.5.10.6.
  
  
  
 4. SHEET S 3 - THERE IS NO ROOF HOOD VENTILATION
 EQUIPEMNT SHOWN ON THE BUILDING ELEVATIONS. PLEASE
 PROVIDE APPROPRIATE DRAWINGS.
  
 5. SHEET S 3 - PROVIDE INDICATION OF THE ROOF STRUCTURE
 MATERIAL. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS
 REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 6. SHEET E 1 - AN EXIT SIGN IS INDICATED IN THE PREP
 ROOM LEADING INTO THE KITCHEN AREA. IT IS NONCOMPLIANT,
 PER CHAPTER 36, 36.2 MEANS OF EGRESS REQUIREMENTS.
  
 36.2.1 GENERAL.
 36.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND THIS CHAPTER.
  
 36.2.5 ARRANGEMENT OF MEANS OF EGRESS.
  
 36.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH SECTION 7.5.
  
 PER CHAPTER 7, 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO
 7.1.9 AND 7.2.1.5.
  
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, 19, 22, OR
 23.
  
  
 THE EXIT SIGN CAN BE PLACED INSIDE THE KITCHEN LEADING
 TO THE PREP ROOM ONLY. PLEASE CORRECT.
  
  
 7. ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE NOTED COMMENTS.
  
  
 PETER LEDUC
 FIRE MARSHAL