Plan Review Notes For Permit 16040042 |
Permit Number |
16040042 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-06 10:24:42 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE SHOW THE REQUIRED EM LIGHTING FOR THE SPACE | | UNDER SCOPE, EITHER BY WALL PACKS OR EM BALLAST. FBC | | 107.3.5 | | 2. SHOW THE RECEPTACLES OUTLETS IN THE SPACE AND LABEL | | EXISTING IF NOT NEW. FBC 107.3.5 | | 3. LABEL CIRCUIT ID DESIGNATION FOR ALL LIGHTING AND | | RECEPTACLE OUTLETS TO CORRELATE WITH PANEL SCHEDULE | | SHOWN. FBC 107.3.5 | | 4. SHOW RTU ON ROOFTOP AND A RECEPTACLE OUTLET WITHIN | | 25FT TO WP/WR GFCI PROTECTED. NEC 210.63 | | 5. CLARIFY IF THERE IS AN EXISTING SHOW WINDOW | | RECEPTACLES PER NEC 210.62 | | 6. FEEL FREE TO CONTACT ME WITH ANY QUESTIONS OR | | CONCERNS. | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|