2016-05-17 08:59:43 | 3RD REVIEW: FBC 2014 5TH ED |
| CHRISTOPHER S. THROOP, C.B.O. |
| BLDG. PLANS EXAMINER ? PX3169 |
| (561) 805-7918 |
| [email protected] |
| |
| 1. PROVIDE FASTENER SCHEDULE FOR WOOD AND DRYWALL |
| REPLACEMENT. |
| 2. PROVIDE REPAIR DETAIL FOR REMOVAL OF CONCRETE SLAB. |
| 3. PROVIDE DETAIL FOR RATED FLOOR/CEILING ASSEMBLY. |
| 4. PROVIDE FLOOR PLAN WITH DEMENSIONS. |
| 5. DESIGNER TO SIGN PALNS. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| R302.3 TWO-FAMILY DWELLINGS. |
| DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE |
| SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR |
| ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR |
| FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED |
| FLOOR/CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND |
| BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES |
| SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF |
| THE ROOF SHEATHING. |
| |
| |