2016-04-29 10:09:55 | 1) SUBMIT A SANITARY DRAINAGE RISER AND A WATER RISER |
| THAT CLEARLY SHOWS THE SCOPE OF PLUMBING WORK TO BE |
| DONE AND HOW IT IS TO BE DONE. THE SUBMITTED DRAWING IS |
| UNACCEPTABLE AND DOES NOT COMPLY WITH THE PLUMBING |
| CODE.FBC 107.1, 107.2.1. THE DRAWING DOES NOT SHOW ALL |
| THE PIPING THAT IS TO BE REPLACED. THERE ARE PLUMBING |
| RISERS AND STACKS AND UNDERGROUND PIPING THAT IS BEING |
| REPLACED THAT IS NOT BEING SHOWN ON THE PLANS. |
| 2) SUBMIT A FLOOR PLAN THAT CLEARLY REFLECTS THE ENTIRE |
| SCOPE OF WORK TO BE DONE.CLEARLY IDENTIFY WHAT WORK IS |
| BEING DONE IN WHAT AREAS. FBC 107.1. |
| 3) SHOW ALL FIXTURE CLEARANCE DIMENSIONS AS REQUIRED BY |
| THE 2014 FBC-PLUMBING SEC. 405.3.1. |
| 4) PLANS SHALL BE SUBMITTED IN DUPLICATE PER THE 2014 |
| FBC-PLUMBING SEC.107.1. |
| 5) THE PLAN SHOWS A FLAT, DRY VENT ON THE SHOWER AND |
| THE WATER CLOSET. VENTS SHALL CONNECT TO THE HORIZONTAL |
| DRAIN PIPE IN ACCORDANCE WITH THE 2014 FBC-PLUMBING |
| SEC.905.3. |
| 6) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER |
| 2014 FBC-PLUMBING SEC.708.3.4. |
| 7) SIZE ALL OF THE DRAIN AND VENT PIPES IN ACCORDANCE |
| WITH THE 2014 FBC-PLUMBING SECS.710.1, TABLE 710.1 (2), |
| 906.1, 906.2. |
| |
| THESE PLANS ARE SEVERELY DEFICIENT IN THE SCOPE OF |
| WORK. DO NOT RESUBMIT JUST THE PLUMBING PLANS FOR |
| REVIEW AGAIN. RESUBMITTED PLANS SHALL ADDRESS ALL THE |
| COMMENTS FROM ALL TRADES. |
| |
| PLEASE REFER TO THE FLORIDA BUILDING CODE WEBSITE FOR |
| FUTHER INFORMATION REGARDING THE ABOVE NOTED CODE |
| SECTIONS AT WWW.FLORIDABUILDING.ORG. |
| |