2016-04-29 11:26:36 | 1ST REVIEW: FBC 2014 5TH ED |
| CHRISTOPHER S. THROOP, C.B.O. |
| BLDG. PLANS EXAMINER ? PX3169 |
| (561) 805-6718 |
| [email protected] |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| |
| 1. PROVIDE FLOOR PLAN WITH DEMENSIONS OF ALL AREAS OF |
| PROJECT THAT WORK SHALL BE PERFORMED. |
| 2. PROVIDE DETAILED SCOPE OF WORK. |
| 3. PROVIDE FASTENER SCHEDULE FOR ALL DRYWALL AND WOOD |
| SHEATHING, (FLOOR & WALLS). |
| 4. PROVIDE DOOR AND WINDOW SCHEDULE FOR ANY REPLACEMENT |
| DOORS &/OR WINDOWS. |
| 5. PROVIDE DETAIL ON TENANT SEPERATION WALLS (FIRE |
| WALL). |
| 6. PROVIDE DETAIL ON HORIZONTAL RATED FLOOR/CEILING |
| ASSEMBLIES. |
| 7. DESIGNER TO SIGN PLANS. |
| 8. ADDITIONAL COMMENTS MAY BE GENERATED UPON REVIEW OF |
| PROPERLY SUBMITTED DOCUMENTS. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |