Plan Review Notes
Plan Review Notes For Permit 16040029
Permit Number 16040029
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-13 15:42:331ST REVIEW 4/13/16
 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE EXISTING DEMAND CALCS ALONG WITH NEW
 ADDITIONAL LOADS, EXISTING RISER DIAGRAM AND PANEL
 SCHEDULES TO INCLUDE CONDUIT , OVERCURRENT PROTECTION
 AND WIRE SIZES.
 - NEC 210.8 A GARAGE OR STORAGE AREAS REQUIRE GFCI
 PROTECTION OF RECEPTACLE OUTLETS
 - NEC 210.70 2B A LIGHTING OUTLET REQUIRED FOR EXTERIOR
 DOORS.
 - SMOKE/CARBON MONOXIODE ALARMS SHALL BE INSTALLED PER
 RESIDENTIAL CODE SECTIONS 314 & 315.
  