Plan Review Notes
Plan Review Notes For Permit 16040024
Permit Number 16040024
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-05 05:36:141) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF WHERE
 THE SLAB WILL BE CUT. FBC 107.2.1.
 2) SUBMIT A SLAB REPAIR DETAIL SHOWING THE MINIMUM AND
 MAXIMUM WIDTHS OF THE AREAS TO BE REPAIRED, THE SIZE OF
 THE REBAR DOWELS TO BE INSTALLED, THE EMBEDMENT DEPTH
 OF THE DOWELS INTO THE EXISTING SLAB, WHAT TYPE OF
 EPXOY WILL BE USED IN THE EMBEDMENT OF THE DOWELS, THE
 SPACING OF THE DOWELS ON CENTER, AND THE THICKNESS OF
 THE SLAB. THIS INFORMATION IS REQUIRED TO ENSURE THE
 INTEGRITY OF THE EXISTING SLAB WILL BE MAINTAINED. FBC
 107.2.1.
 3) THE SOIL SHALL BE TREATED FOR TEMITES PRIOR TO THE
 POURING OF ANY CONCRETE. 2014 FBCR SEC. R 318.
 4) A MINIMUM 6 MIL VAPOR RETARDER SHALL BE PLACED OVER
 THE SOIL PRIOR TO POURING ANY CONCRETE. 2014 FBCR
 SEC.R506.2.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR