Plan Review Notes
Plan Review Notes For Permit 16031479
Permit Number 16031479
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-04 09:33:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16031479
 ADD: 1501 N. AUSTRALIAN BLVD.
 CONT: HI-TECH ROOFING & SHEET METAL, INC.
 TEL: 561-586-3110
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 04/2016
 ACTION: DENIED
  
 1) UNDER THE SCOPE OF WORK THE DOCUMENT INDICATES THE
 CONTRACTOR SHAL REPAIR OR REPLACE PORTIONS OF THE ROOF
 MEMBRANE COVERING.
 PLEASE UPDATE NOTES THE ROOF WILL EITHER BE REPAIRED.
 THE ROOF WILL BE REPLACED, THE WORD OR CANNOT BE USED
 IN THE DESCRIPTION OF WORK. PLEASE REVIEW 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 SECTION 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 2) PLEASE PROVIDE THE SQUARE FOOTAGE OF THE ROOF WHERE
 WORK IS TO OCCUR. THE SQUARE FOOTAGE AREA OF WORK IS
 OVER THE 255 SQ. FT LISTED IN THE 11 WORK AREAS LISTED
 ON EXHIBIT A. ITEM (I) ALONE IS 255 SQUARE FEET ALONE,
 85 SQ. FT. X3= 255 SQ. FT. 2014 FBC-EXISITNG BUILDING
 CODE
 708.1.1 NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA
 OR ROOF SECTION OF ANY EXISTING BUILDING OR STRUCTURE
 SHALL BE REPAIRED, REPLACED OR RECOVERED IN ANY
 12-MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR
 ROOF SECTION CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 3) EXHIBIT A NOTE (F) INDICATES THE REMOVAL OF CLEAN
 AND RESEAT/ RESEAL ALL ROOF DRAINS (6). PLEASE EXPLAIN
 IF THE MATERIALS USED IN SEATING OF THE ROOF DRAINS ARE
 USED? REMOVAL OF, CLEAN AND RESEAT SOUNDS LIKE THEY ARE
 USED MATERIALS?
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED,
 RECYCLED, OR RECLAIMED MATERIALS WHICH MEET THE
 REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE
 REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL.
  
 2014 FBC-EXISITING BLDG. CODE 602.2 NEW AND REPLACEMENT
 MATERIALS. EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY
 THIS CODE, MATERIALS PERMITTED BY THE APPLICABLE CODE
 FOR NEW CONSTRUCTION SHALL BE USED. LIKE MATERIALS
 SHALL BE PERMITTED FOR REPAIRS AND ALTERATIONS,
 PROVIDED NO DANGEROUS OR UNSAFE CONDITION, AS DEFINED
 IN CHAPTER 2, IS CREATED. HAZARDOUS MATERIALS, SUCH AS
 ASBESTOS AND LEAD-BASED PAINT, SHALL NOT BE USED WHERE
 THE CODE FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR
 USE IN BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND
 LOCATION.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 4) THE EXHIBIT A NOTE (E) INDICATES INSTALL ADDITIONAL
 HVAC CURB FLASHING PLEASE PROVIDE COMPLIANCE WITH:
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 5) NOTES B & C BOTH DEAL WITH THE HVAC DUCTWORK STANDS
 AND HVACMEMBRANE WRAPS AROUND THE HVAC SUPPLY AND
 RETURNS. AGAIN PLEASE SUPPLY DOCUMENTS THAT ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.107.2.1.2.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  