2016-04-06 08:01:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / NEC 2008
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS INDICATE A MAIN LUG ONLY PANEL AND NO MAIN
 BREAKER OR DISCONNECT IS SPECIFIED. A DISCONNECT AND
 /OR MAIN BREAKER IS REQUIRED TO PROVIDE OVERCURRENT
 PROTECTION FOR THE SERVICE ENTRANCE CONDUCTORS. NEC
 230.70 & 230.91
  
 2) THE PANEL SCHEDULE FEEDER SIZE IS LISTED AS 3/0 AND
 THE RISER HAS 2/0. PLEASE CORRECT. FBC 107.2.1
  
 3) THE ELECTRICAL NOTES SPECIFY THE 2012 NEC AND THIS
 PROJECT IS SUBJECT TO THE 2008 NEC. PLEASE CORRECT.