2016-03-30 18:07:02 | JOB PERMIT NUMBER: 16031398 |
| JOB ADDRESS: 513 58TH ST |
| WEST PALM BEACH FL |
| DATE: MARCH 30 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - NEC 210.52 A 1 & 2 OUTLET SPACING, IT APPEARS SOME |
| POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET ( MARKED |
| ON PLANS RED INK ) |
| - NEC 210.52 H IN DWELLING UNITS HALLWAYS 10 FT OR OR |
| MORE SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET. ( |
| MARKED ON PLANS RED INK ) |
| - NEC 210.E 1 FOR A ONE & TWO FAMILY DWELLING UNIT AT |
| LEAST ONE GFCI RECEPTACLES IN THE FRONT AND BACK OF THE |
| DWELLING . ( MARKED ON PLANS RED INK ) |
| - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS |
| 314 & 315 ( MARKED ON PLANS RED INK ) |
| - ADD INTERSYSTEM BONDING TERMINAL TO RISER DIAGRAM |
| GROUNDING DETAIL NEC 250.94 |
| - NEC 210.12 B AFCI PROTECTION REQUIRED. CHECK ALL |
| AREAS APPLICABLE. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6713 |