Plan Review Notes For Permit 16031335 |
Permit Number |
16031335 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-30 14:21:00 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - PROVIDE A FIXTURE SCHEDULE AND MANUFACTURE SPECS OF | | TRANSFORMER BEING INSTALLED.KEEP IN MIND THAT IF | | TRANSFORMER ARE OUTSIDE IT SHALL PROTECTED BY A GFCI. | | WBPA 107 | | | | - PROVIDE WIRING METHOD BEING USED SUCH AS WIRE SIZE , | | TYPE , AND INSULATION TO COMPLY WITH NEC 411. | | | | - " NOTE" EVEN THOUGH LANDSCAPE LIGHTING IS EXEMPT FROM | | FLORIDA ENERGY CODE ITS HIGHLY RECOMMENDED TO PUT ON A | | ASTRONAMICAL DIGITAL TIMER OR COMBINATION PHOTOCELL / | | TIMER. |
|